Install Instructions
43
BOILER DIMENSIONS & RATINGS
Table 11.3: Series 63™ Boiler Ratings
1. Net Ratings are based on DOE Heating Capacity less an allowance for normal piping and pickup as determined by the
Testing and Rating Standard for Low Pressure Cast Iron Heating Boilers of the Hydronics Institute. Water ratings are based on
a piping and pickup factor of 1.15. Steam ratings are based on a piping and pickup factor of 1.33. Consult PB Heat before
selecting a boiler for gravity hot water installations or for installations having unusual piping and pickup requirements such as
exposed piping, night set back, etc. Ratings shown are for elevations up to 2,000 feet. For elevations above 2,000 feet, ratings
should be reduced at the rate of 4% for each 1,000 feet above sea level.
2. Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government tests. Before
purchasing this appliance, read important information about its estimated annual energy consumption or energy efficiency
rating that is vailable from your retailer.
Series 63™
Boiler
Model
Input,
MBH
Heating Capacity³ Net Ratings¹ AFUE²
Water,
MBH
Steam,
MBH
Steam,
sqft
Steam,
MBH
Water,
MBH
Water,
%
Steam,
%
63-03L 88.5 73 74 233 56 63 82.4 83.0
63-03 118.0 99 98 308 74 86 83.5 82.6
63-04L 147.5 123 123 383 92 107 82.7 82.6
63-04 177.0 148 147 458 110 129 83.4 82.4
63-05L 206.5 172 171 533 128 150 82.9 82.3
63-05 236.0 198 196 613 147 172 83.3 82.2
63-06 287.5 241 238 746 179 210 83.2 82.0
Water
Content
Approx.
Shipping
Weight,
lb
Water,
gal
Steam,
gal
13.2 9.3 465
13.2 9.3 465
15.6 10.8 576
15.6 10.8 576
18.0 12.4 700
18.0 12.4 700
20.4 13.9 812
Series 64™
Boiler
Model
Input,
MBH
Gross Output² Net Ratings¹
Thermal
Efficiency
Combustion
Efficiency²
Water,
MBH
Steam,
MBH
Steam,
sqft
Steam,
MBH
Water,
MBH
Water,
%
Steam,
%
Water,
%
Steam,
%
64-07 345 286 274 858 206 249 81.0 79.4 83.0 82.5
64-08 399 331 318 996 239 288 81.0 79.6 83.0 82.5
64-09 460 382 367 1146 275 332 81.0 79.7 83.0 82.5
64-10 518 430 413 1292 310 374 81.0 79.8 83.0 82.5
64-11 575 477 459 1433 344 415 81.1 79.8 83.0 82.5
64-12 633 525 506 1583 380 457 81.0 79.9 83.0 82.4
Water
Content
Approx.
Shipping
Weight,
lb
Water,
gal
Steam,
gal
22.8 15.5 945
25.2 17.0 1081
27.6 18.6 1218
30.0 20.1 1354
32.4 21.7 1490
34.8 23.2 1527
1. Net Ratings are based on Gross Output less an allowance for normal piping and pickup as determined by the Testing and
Rating Standard for Low Pressure Cast Iron Heating Boilers of the Hydronics Institute. Water ratings are based on a piping
and pickup factor of 1.15. Steam ratings are based on a piping and pickup factor of 1.33. Consult PB Heat before selecting a
boiler for gravity hot water installations or for installations having unusual piping and pickup requirements such as exposed
piping, night set-back, etc. Ratings shown are for elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should
be reduced at the rate of 4% for each 1,000 feet above sea level.
2. Combustion efficiency and gross output are determined in accordance with ANSI Z21.13 / CSA 4.9, Gas-Fired Low-Pressure
Steam and Hot Water Boilers.
Table 11.4: Series 64™ Boiler Ratings