HydroStat User Guide

9
IGNITION LED LEGEND and OPERATION
PROPER PILOT FLAME

LIMITS Illuminates on a call for heat to indicate the
external limits are satisfied. (External limits may include flame
rollout, spill switch, secondary low water cut-off etc.). If the
external limits are open, the LIMITS light will blink.
V-PWR Indicates power has been sent to the vent
damper (Model 4200a) or the inducer motor (Model 4200i).
V-SW Illuminates when the vent damper switch (on an
atmospheric boiler) or the air pressure switch (on an induced
draft boiler) has made. If the damper end switch (Model
4200a) or the air pressure switch (Model 4200i) fail to make
in 30 seconds, the V-SW light will blink.
FLAME Illuminates when the pilot flame is lit. If the pilot
flame is not sensed within 75 seconds or if flame is lost, the
FLAME light will blink.
A properly adjusted pilot should have a blue, steady flame
with an inner cone that engulfs 3/8" - 1/2" of the flame rod.
The flame rod should glow bright orange from the heat and
the flame current should be higher than 2.0 µA.
Note: To read flame current see TEST/SETTINGS button on
page 8.
If the pilot flame is over sized, orange in color, and blowing far
beyond the flame rod then the pilot is over fired. The flame cur-
rent will read outside of the nominal range and the pilot should
be adjusted down.
If the flame is small and the inner cone does not engulf the
flame rod then the pilot is under fired. When the pilot is under
fired, the flame rod does not glow bright orange. The flame
current will read below 1.0 µA and should be adjusted up to a
value higher than 2.0 µA.
Note: If the flame current reads below 0.8 µA, the control will
continue to spark as it does not recognize an acceptable
flame current.
Refer to the gas valve manufacturer’s instructions for adjust-
ing the gas valve.
3/8" to 1/2" Flame Coverage
Flame Rod
LIMITS V-PWR V-SW FLAME
IGNITION