Submittal Sheet
Optional Equipment:
❑ PFA-1 Interface Adapter
▪ Alarm Contacts
▪ Analog Input
▪ Modbus Communications
❑ 3" Concentric PVC Vent Termination
❑ Steel Stand Convertible for Wall Mounting
❑ Domestic Water Tank Temperature Sensor
❑ System Sensor for Multiple Boiler Operation
❑ Boiler Circulator
❑ 50 PSI Safety Relief Valve
❑ 100 PSI Safety Relief Valve
❑ 150 PSI Safety Relief Valve
❑ PC Software
▪ Status
▪ Fault History
❑ Probe-Type Low Water Cutoff
❑ Expansion Tank
❑ High Performance Air Vent
PEERLESS
®
PUREFIRE
®
HIGH EFFICIENCY STAINLESS STEEL BOILER
SERIES PEERLESS
®
PUREFIRE
®
BOILER RATINGS
Boiler
Input (MBH)
Heating
Capacity
(MBH)
Net
Ratings
(MBH)
AFUE
(%)
Min Max
PF-210 42 210 193 168 93.3
SERIES PEERLESS
®
PUREFIRE
®
CAPACITIES
Gas Pressure
Min/Max
(Inch WC)
Total Water
Capacity
(Gallons)
Minimum Water Flow Rate
(40ºFDT)
Total Combined
Length of Air
Intake & Vent
(Feet)
Shipping
Weight
(Lbs)
Flow Rate
(GPM)
Pressure Drop
(Feet)
3.5 13.5 1.19 9.6 6.23 200 165
SERIES PEERLESS
®
PUREFIRE
®
ELECTRICAL RATINGS
Supply
Voltage
(-15%, +10%)
Frequency
(±1.2 hz)
Blower Gas Valve Pumps
Max Total
Service
Current to Boiler
Voltage
(VAC)
Current
(Amps)
Voltage
(VAC)
Current
(Amps)
Voltage
(VAC)
Max.
Current
(Amps)
120 VAC 60 hz 120 2.58 120 0.09 120 3.06 5.73
These specifications are subject to change without notice.
PF8120 R2 (12/12)
Printed in U.S.A.
©2012 PB Heat, LLC. All rights reserved.
CONTROLS