FOR DIRECT ATTACHMENT TO LOAD BEARING
CONCRETE ONLY! Concrete expansion anchors are
not intended for attachment to concrete ceilings
covered with a layer of plaster, drywall, or other
finishing material. If mounting to concrete ceiling
covered with plaster / drywall is unavoidable, plaster /
drywall must be counterbored as shown below.
WARNING
B
A
CONCRETE CEILING
Drill hole and insert anchor
Place ceiling plate over anchor and secure with screw
After repeating step one tighten all fasteners
Tighten wood screws so that wall plate is firmly
attached, but do not overtighten. Overtightening can
damage the screws, greatly reducing their holding
power.
Never tighten in excess of 80 in • lb (9 N.M.).
Make sure that mounting screws are anchored into the
center of the studs. The use of an "edge to edge" stud
finder is highly recommended.
WARNING
When installing Peerless wall mounts on concrete, verify that you have a minimum of 1 5/8" of actual concrete surface
in the 1/4" diameter hole to be used for the concrete anchors. Do not drill into mortar joints! Concrete must meet
ASTM C-90 specifications.
Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete anchor.
Installer must verify that the supporting surface will safely support the combined weight of mount and projector.
Never exceed the Maximum Load Capacity of 50 lb (22.7 kg).
WARNING
Drill two 1/4" (6 mm) dia. holes to a minimum depth of
2.5" (64 mm). Attach ceiling plate (A) using two
concrete anchors (F) and two #14 x 2.5" wood screws
(B) as shown in Illustration A and 1, 2, and 3 (below).
Tighten all fasteners.
Installation to Concrete Ceilings