Install Instructions

© COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED. P/N 69387 3220-2124 REV 2 PAGE 2
JP4 Jumper Selection – 2 or 4 Pipe Operation: Connection of a pipe sensor
will change the operation of the outputs as shown in the table below. (See
Technical Notes for further information on Pipe Sensor Operation)
2-Pipe Operation - Install JP4 - The thermostat will permanently disable
the Secondary Output and disables system and fan invalid modes.
4-Pipe Operation - Remove JP4 - Both the Main Output (COOL) and
Secondary Output (HEAT) will be available.
JP4
Selection
Pipe
Sensor
Water
Temp
Aqua
Stat
Main Output
(Blue Wire)
Secondary
Output
(Red Wire)
COLD
Open
Cooling ONLY
Disabled
2-Pipe
JP4-ON
HOT
Closed
Heating ONLY
Disabled
COLD
Open
Cooling
Heating
4-Pipe
JP4-OFF
HOT
Closed
Heating ONLY
Disabled
Condensate Overow Interrupt - The remote probe input can be used with a
condensate overow interrupt switch (CO), either in conjunction with a remote
probe (normally closed CO switch) or with local sensing (normally open CO
switch). When the condensate switch activates, the T180 will display the
service wrench and disable all outputs
White/Yellow
White/Violet
Remote Probe
Circuit Common
Normally
Closed
Condensate
Switch
Rem ote Probe Installation
White/Yellow
White/Violet
Remote Probe
Circuit Common
Normally
Open
Condensate
Switch
Local Sensor Installation
Mounting Thermostat
Thermostat mounts to a 4” x 4” box with a 2” x 4” mud ring. Adapter
wall plates are available if needed.
Pull wires through the hole of the thermostat base.
Mount thermostat base to the wall using the enclosed mounting
screws. Tighten screws evenly but do not over tighten.
Verify that the circuit board is rmly snapped into the cover and has not
been dislodged during handling.
Match and connect equipment wire thermostat using the appropriate
wiring schematic as shown at the bottom of the page on the left-hand
side.
Wire nut all unused wires or terminate properly according to local
building codes.
1.
2.
3.
4.
5.
6.
!
Mount the base to the mud ring and install the cover assembly. Firmly
press cover to engage the cover locking snaps. Should the cover need
to be removed in the future, use a at edged tool to put pressure on the
base sides. This will release the four side latches.
Turn on power to equipment.
CAUTION
2x4 Mud Ring
T180 Base
T180 Cover Assembly
All wiring connections must be made
inside the electric box or the T180
maybe damaged.
Cover Locking Snaps
(Both Sides)
System Check-out
After wiring and installation is complete, energize the system.
Set fan to ON. Select each fan speed (TA180 Models) to verify
operation.
Set the System button to AUTO, or available selection.
Using the UP arrow, adjust temperature more than 5°F above the
room temperature to cycle on heating.
Using the DOWN arrow adjust the temperature to 5°F below room
temperature to cycle on cooling.
Note: If the thermostat is set to utilize a time-based purge cycle (Service
menu 16), the thermostat will conduct a 3-min purge on initial start-up if a pipe
sensor is connected.
THERMOSTAT CONFIGURATION / SERVICE MENU
To enter the Service Menu press the UP and DOWN arrows simultaneously
for ve (5) seconds. The current display icon will be turned off.
Service menu number 1 will appear. Push the SYSTEM button to move to the
next Service Menu number. The UP and DOWN arrow keys will scroll through
your range of options for each feature. All changes to the Service Menu are
automatically saved when the system times out. Please refer to the service
menu table on page three.
USER OPERATION
Please refer to T180 Programmable Thermostat Owner’s Manual for
operating instructions
TECHNICAL / APPLICATION NOTES
Standard Fan Operation:
7.
8.
1.
2.
3.
4.
5.
Black
Yellow
White/Black
White/Blue
White/Gray
Blue
Red
White/Brown
White/Red
White/Orange
Brown
L1
L2 / NEUTRAL
Setback Input/ Door Switch
Pipe Sensor
Occupancy Detector
Cool
(
Main Output)
Heat
(Secondary Output)
Fan Low
Fan Medium
Fan High
Outside Air
THERMOSTAT CONNECTIONS
LOW VOLTAGE LINE VOLTAGE
White/Yellow
White/Violet
Remote Probe
Circuit Common
OUTPUTS
See Ratings
Accessories
Available
from
PECO