MENU FEATURE OPTIONS STD.MODEL
DEFAULT
DESCRIPTION / COMMENTS
460 Heat Recovery Rate 0-18°F/Hr
0-10°C/Hr
0°F/Hr Denes the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp
recovery.
470 Cool Recovery Rate 0-18°F/Hr
0-10°C/Hr
0°F/Hr
Denes the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp
recovery.
480 Minimum Off Time 1-10 minutes 4 minutes Sets the minimum off time for both the heat and cool output.
490 Humidity Control
Enable
(Select models only)
0-3 0 Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal
becomes dehumidify. Note: If option 3 is selected, Service Menu 491 becomes available.
0 = Disabled
1 = Dehumidify Control
2 = Humidify Control
3 = Dehumidify and Humidify Control
491 Humidity Deadband 10-50 30% relative
humidity (RH)
Selects the deadband in %RH between the humidify and dehumidify setpoints. Note: If option 3 is
selected in Service Menu 490, Service Menu 491 becomes available.
10; 20; 30; 40; 50
500 Programmable/
Intermittent Fan
0-2 0 0 = Disable
1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in
unoccupied periods.
2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.
501 Intermittent Fan On
Time
1-60 minutes 5 minutes Denes the on time for the Intermittent Fan.
502 Intermittent Fan Off
Time
0-60 minutes 25 minutes Denes the off time for the Intermittent Fan. Select 0 for continuous fan.
510 Power Harvesting
Enable
(For use on systems
in which a Common
“C” power wire is
unavailable)
0-3 0 Options 1-3 draw a small amount of current from load wire indicated to supplement battery supply.
0 = No power harvesting is available.
1 = Use Y1 as the battery supplement.
2 = Use W1 as the battery supplement.
3 = Use both Y1 and W1 as the battery supplement
520 Default Display
Icons
0-4 0 Select icons that will be displayed in the Default Display screen.
0 = Time, Temp, SP
1 = Time, Temp
2 = Time
3 = Temp
4 = None
530 Revision Displays rmware revision information (for technician); not adjustable.
540 Factory Default
Reset
0,1 0 Select 1 (enable) to restore factory default settings for thermostat. Select 0 to disable.
0 = Disable
1 = Enable
Note: Press “Done” key to complete process.
600 System Test Main
Output (Cool)
0-2
0
Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu
to disable.
0 = Disable
1= Cool Stage 1
2 = Cool Stage 2
610 System Test Main
Output (Heat)
0-3 0 Select an option to activate the fan output for 10 minutes; select 0, Done or a different Service Menu
to disable. Note: Outputs will be activated based upon the system conguration.
0 = Disable (Default)
1 = Heat Stage 1
2 = Heat Stage 2
3 = Heat Stage 3
620 System Test Fan
Output
0,1 0 Select 0 or 1 to activate the fan output for 10 minutes; select 0, Done or a different Service Menu to
disable.
0 = Disable Fan Output
1 = Enable Fan Output Note: Outputs will be activated based upon the system conguration.
630 System Test
Emergency Output
0,1 0 Select 0 or 1 to activate the Emergency output for 10 minutes; select 0, Done or a different Service Menu to
disable.
0 = Disable Emergency Output
1 = Enable Emergency Output
640 System Test
Economizer
0,1 0 Select 1 to activate the Economizer output for 10 minutes; select 0, Done or a different Service Menu to
disable.
0 = Disable Economizer Output
1 = Enable Economizer Output
Warning: Power Harvesting is intended to be used only as a
battery supplement. If enabled, the feature preserves battery
life. If Power Harvesting is not compatible with your system,
select “0” (default) to disable. If thermostat is powered from AC,
select only “0” or off. Consult a technician if you have
questions.