Install Instructions

© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 69563 3220-2181 REV 00
2
OPERATING INSTRUCTIONS
Idle Display
No action
Continuously displays the current zone temperature or setpoint
Change setpoint
Repeatedly press UP or DOWN arrow button
SETPOINT ashes
Display increases or decreases
Release and system returns to the idle display
Begin Timed Override
Press and hold the ON button until OVERRIDE appears
Timed override begins
System shows the idle display and OVERRIDE
Cancel Timed Override
Hold CANCEL button until OVERRIDE disappears
Timed override is cancelled
System returns to the idle display
Change display units (°F/°C)
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (current unit ashing)
Press UP or DOWN button to select °F and °C
Selected unit begins ashing
System returns to the idle display
Change idle display from room temperature display to continuous
setpoint display mode
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (current unit ashing)
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (not ashing)
Press UP or DOWN arrow buttons
SETPOINT ashes
Display times out and returns in the continuous setpoint display
mode
Adjust the setpoint offset
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (current unit ashing)
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (not ashing)
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows the setpoint adjust mode
Hold UP and DOWN arrow buttons
Setpoint offset value changes
System returns to the idle display
Adjust the room temperature display offset
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (current unit ashing)
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows °F and °C (not ashing)
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
SETPOINT ashes
Display shows the setpoint adjust mode
Hold UP and DOWN arrow buttons until screen goes blank
Release buttons
Display shows temperature offset display
Press UP or DOWN arrow buttons
Temperature offset value changes
System returns to the current display mode
SERVICE INSTRUCTIONS
Balancing Functions:
The* and ** functions allow balancing functionality at the zone sensor. See table below:
Engage Function Disengage Function Display Shows Override Function Depends on Controller Type
Press “ON” and “UP”
simultaneously until screen
goes blank
Press “UP” or “DOWN” until
normal display returns
*
UCM 4.x VV550/551
Drive air valve to maximum
primary airow
Drive air valve to minimum
primary airow
Press “ON” and “DOWN”
simultaneously until screen
goes blank
Press “UP” or “DOWN” until
normal display returns
**
Drive unit to unoccupied (both ow
and temperature setpoints).
Drive air valve to maximum
primary airow
PECO is a registered trademark of PECO, Inc. The PECO logo is a trademark and/or service mark of PECO, Inc.