Accessory List
MA40-717x Series
84
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Specifications
Accessories
Typical Applications
Inputs
Control signal On-off SPST control contacts or Triacs (500 mA) rated.
Power Refer to Model Chart.
Connections 2 ft (61 cm) long appliance cable & 1/2 in. conduit connectors.
Outputs
Motor Type Brushless DC.
Mechanical
Direction of rotation: CW or CCW rotation is available through reverse mounting.
Dual shaft clamps: Direct coupled using a through hole output hub.
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: -25 to 140°F (-32 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA 1, NEMA 4 (IEC IP56) with customer supplied water tight connector.
Agency Listings
UL
UL-873, Underwriters Laboratories Listed (File #9429 Category Temperature-Indicating and
Regulating Equipment).
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). Not applicable to MA40-7170.
CSA Canadian Standards C22.2 No. 4-93.
Australia
This product meets requirements to bear the C-Tick mark according to the terms specified by the
Communications Authority under the Radio Communications Act 1992.
General Instructions Refer to F-26742.
Model No. Description
AM-674 Weather shield.
AM-676 Universal shaft extension, approximately 9-1/2 in. long (242 mm) for use on 3/8 to 11/16 in. (10 to 17 mm)
round shafts, 3/8 to 9/16 in. square shafts. (AM-753 clamps required).
AM-751 Standard anti-rotation bracket 9 in. long x 13/16 in. wide (229 x 21 mm), included with actuator.
AM-752 Optional anti-rotation bracket 4 in. long x 1-11/16 in. wide (102 x 43 mm), for narrow spaces.
AM-753 Optional damper shaft mounting clamps for 5/8 in. square shaft, 3/4 in. and 1 in. round shafts (two per
package).
AM-754 Standard universal mounting clamps for 3/8 to 1/2 in. (10 to 13 mm) round and square shafts, two included
with actuator.
AM-756 Metric conduit adaptor M20 x 1.5 to 1/2 in. NPT (two per package).
AV-602 Vx-7xxx 1-1/2 to 2 in. valve linkage.
AV-607 Vx-9xxx 2-1/2 to 4 in. valve linkage.
MA40-717x
Black
Black/Blue
24H
24G
24 Vac
GRDGreen/Yellow
1
2
3
4
1 SPST or Triac Controller. Multiple MA40-7173
actuators may be powered by a single 24 Vac
transformer.
2 Unused conduit port must remain plugged with a
water tight pipe plug as shipped from factory to
maintain NEMA Type 4 or IP56 rating.
3 Ground wire may be Green on some models.
Voltage Wire Wire
(H) or L1) (G) or L2)
24 V Black Black/Blue
120 V Black White
240V Brown Light Blue
4
Figure 1 Typical Wiring Diagram for MA40-717x.