Accessory List
MA40-704x Series, MA41-707x Series, and MA41-715x Series
80
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Specifications
Inputs
Control signal On-off SPST contacts or Triacs (500 mA).
Power Refer to Model Chart.
Connections
3 ft. (0.9 m) long, appliance cable, 1/2 in. conduit connectors. For M20 Metric conduit, use AM-756
adaptor.
Outputs
Motor Type
MA40-704x, MA41-707x: Brush.
MA41-715x: Brushless DC.
Electrical
MA40-7043-501: One auxiliary switch available, SPDT 6A resistive @ 24 Vac, adjustable 0 to 95° (0 to
1 scale). UL listed, switch meets VDE requirements for 6 (1.5)A, 24 Vac.
MA40-7040-501 or MA40-7041-50: One auxiliary switch available, SPDT 6A resistive @ 240 Vac,
adjustable 0 to 95° (0 to 1 scale). UL listed, switch meets VDE requirements for 6 (1.5)A, 24 Vac.
MA41-715x-502 or MA41-707x-502: Two auxiliary switches available, SPDT 7A resistive @ 250 Vac,
one fixed @5 ° and one adjustable 25 to 85°. UL Listed, meets VDE requirements for 7 (2.5)A, 250
Vac.
Mechanical
Direction of rotation: CW or CCW rotation is available through reverse mounting.
Shaft clamp: Direct coupled using a through hole output hub.
MA40-704x: Up to 5/8 in. round, 1/2 in. square shafts.
MA41-71xx: Up to 3/4 in. round, 1/2 in. square shafts.
See Accessories for larger shaft options.
Position Indicator: MA40-704x: Visual indicator, 0 to 1 (0 is the spring return position).
MA41-707x, MA41-715x: Pointer (-5 to 90°) and scale are provided for position indication (-5 is normal
or spring return position).
Environment
Ambient Temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: -22 to 140°F (-30 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations
MA40-704x: NEMA 2 (IEC 1P54) no restrictions.
MA41-707x: NEMA 1 (IEC IP30), NEMA 2 (IEC IP54) with conduit in the down position.
MA41-715x: NEMA 1 (IEC IP30), NEMA 2 (IEC IP54) with conduit in the down position.
Dimensions
MA41-707x, MA41-715x: 10-1/2 H x 4 W x 3-1/2 D in. (287 x 100 x 89 mm).
MA40-704x: 6-51/64 H x 4 W x 3-1/2 D in. (68 x 100 x 89 mm).
Agency Listings
UL
UL-873, Underwriters Laboratories Listed (File #E9429 Category Temperature-Indicating and
Regulating Equipment).
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
CUL Canadian Standards C22.2 No. 24-93.
Australia
This product meets requirements to bear the C-Tick mark according to the terms specified by the
Communications Authority under the Radio Communications Act 1992.
General Instructions Refer to F-26642.