Accessory List
MA4D-xxxx Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 75
Specifications
Accessories
Typical Applications
Inputs
Control signal Two-Position SPST.
Power See Model Chart. All 24 Vac circuits are Class 2. All circuits 30 Vac and above are Class 1.
Connections
3 ft (91 cm) appliance or plenum cables, enclosure accepts 1/2 in. (13 mm) conduit connector. For M20
Metric conduit, use AM-756 adapter.
24 Volt models: 10 ft. plenum cable.
Outputs
Mechanical
Timing: See Model Chart.
Travel: 93
o
nominal.
Manual Override: Allows positioning of damper or valve using manual crank.
Environment
Ambient temperature limits
Shipping and Storage: -40 to 160°F (-40 to 71°C).
Operating: -22 to 140°F (-30 to 60°C).
Humidity 15 to 95% RH, non-condensing.
Locations
NEMA 1, NEMA 2, UL Type 2 (IEC IP54) with customer supplied water tight conduit connectors.
Enclosure is air plenum rated.
Dimensions 7-7/8 H x 3-1/2 W x 3-1/2 D in. (200 x 89 x 89 mm).
Agency Listings
UL 873 Underwriters Laboratories (File #E9429 Category Temperature-Indicating and Regulating Equipment).
CUL UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards C22.2 No. 24-93.
European Community
EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). This product fits in Installation
Category (Overvoltage Category) II per EN 61010-1.
Australia
This product meets requirements to bear the C-Tick Mark according to the terms specified by the
Communications Authority under the Radiocommunications Act 1992.
General Instructions Refer to F-27170.
Model No. Description
AM-714 Weathershield kit.
AM-756 Metric conduit adapter M20 x 1.5 to 1/2 in. NPT.
AM-771 Crank arm and bracket kit.
AM-772 Bracket for reverse mounting.
MA4D-x033-x00
Blk
Blue
Voltage
L1 N
MA4D-x03x-000
L2 Hot
120 Vac
230 Vac
White Black
Brown
Com
Red
Hot (+DC)
SPST Control Contact
1
1
Line
Volts
24 Vac Transformer
or 20-30 Vdc
L1
L2
N
Hot
120 Vac or
230 Vac
SPST Control Contact
Figure 1 Typical Wiring Diagrams for Two Position Actuators.