Specifications
Mounting
Directly to an actuator. The drive may be mounted on either the left or right side of the actuator, in a
conduit opening adjacent to the low voltage wiring compartment.
Case Injection molded plastic with stamped aluminum cover.
Inputs - Voltage and Current
Input Refer to Model Chart.
Input Span Adjustment Refer to Model Chart.
Start Point Adjustment Refer to Model Chart.
Input Impedance
Voltage Input Greater than 10,000 ohms.
Current Input 250 ohms.
Power Supply
Power shall be supplied directly from the shading coil windings provided on the shaded pole
reversible motor of the gear train actuator (less than 30 Vac).
Outputs
Connections
Color-coded leads with crimped screw terminal connectors.Purge override (input signal override)
leads are color-coded pigtails.
Shading Coil Triac Output 1.2 A RMS.
Deadband Refer to Model Chart.
Environment
Ambient temperature limits
Shipping & Storage -40 to 160
o
F (-40 to 71
o
C).
Operating -40 to 136
o
F (-40 to 58
o
C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 4; IEC IP56.
Agency Listings
UL Listed UL 873 (File #E9429 Category Temperature Indicating and Regulating Equipment).
CUL Canadian Standards C22.2 No. 24-93.
European Community EMC Directive 89/336/EEC.
General Instructions Refer to F-26563.