Accessory List
CP-9301-xxx Series, CP-9302-xxx Series
66
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Electronic Actuator Drive
Model Chart
a
Units with a “-2” suffix, e.g. MP-xxxx-xxx-2-x, include a built-in transformer (used for Microtherm
®
or with AE-504) with secondary leads wired externally to terminals 7 (Blue, 12 Vac) and 8
(Red, 24 Vac) of the actuator.
Caution:
When using the CP-9301 or CP-9302 with actuators containing an
internal transformer,
disconnect and tape off the red and blue leads before installing and powering the device.
Failure
to do so can result in damage to the actuator drive
.
Note:
Models prior to “-2” suffix had transformer wired directly to potentiometer. To disconnect the transformer, remove the back plate of the actuator, then disconnect and tape the transformer
leads.
The CP-9301 and CP-9302 electronic actuator drives
process a variable input signal from a controller to provide
proportional control of an electric gear train actuator. The
CP-9301 is preset at the factory for voltage input. The CP-
9302 is factory preset for current input and has additional
wiring for connection to an override switch, for those
applications requiring an external override of the input
signal. These drives are equipped with built-in jumpers
and adjustable potentiometers, so that the type of input
signal, deadband, input span, and start point may be reset
in the field when necessary.
Features:
• Mounts directly onto TAC proportional, electric, gear train actuators.
• Power is supplied directly from the actuator.
• Jumpers for selecting either voltage or current input, as well as 3%
or 5% deadband.
• Adjustable span and start point potentiometers.
Part Number
Input Signal
Override
Factory Jumper Settings Jumper Settings
Potentiometer
Adjustment Ranges
Input
Signal
Deadband Start Point Input Span
Input
Signal
Deadband Input Span Start Point
CP-9301
Not Available
Voltage
(6 to 9 Vdc)
3% of Input
Span
6 Vdc 3 Vdc
Voltage
or
Current
3% or 5% of
Input Span
3.0 to 16.5
Vdc or 8 to
16 mAdc
0 to 10 Vdc
or 2 to 16
mAdc
CP-9301-456
Voltage
(0 to 10
Vdc)
0 Vdc 10 Vdc
CP-9302 Available
(Use is
Optional)
Current
(4 to 20
mAdc)
4 mAdc 16 mAdc
CP-9302-702
5% of Input
Span
Typical Actuators.
Actuator Series
Power Torque
Stroke
Degrees
Spring
Return
Internal
Transformer
a
Vac
60 Hz
Amp Lb-in. N-m
MP-2113-500 24 2.2 50 5.6 180 ⎯ No
MP-361 24 2.5 50 5.6 180 CW No
MP-371 24 2.5 50 5.6 180 CCW No
MP-381 24 2.5 220 24.9 180 ⎯ No
MP-9713 24 4.0 800 90.3 180 ⎯ No
MP-465 120 0.5 50 5.6 180 CW Yes
MP-475 120 0.5 50 5.6 180 CCW No
MP-483 120 0.5 220 24.9 90 ⎯ Yes
MP-485 120 0.5 220 24.9 180 ⎯ Yes
MP-495 120 0.95 450 50.8 180 ⎯ Yes
MP-9750 120 0.9 800 90.3 180 ⎯ Yes
MP-4651 240 0.25 50 5.6 180 CW Yes
MP-4851 240 0.25 220 24.9 180 ⎯ Yes
CP
-
9301
xxx
Series,
CP-9302
xxx Seri
e