Accessory List
CP-8551, CP-8552
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 65
Accessories
Typical Applications
Figure 1 CP-8551 Typical Wiring.
Figure 2 CP-8552 Typical Wiring for Voltage Input.
Figure 3 CP-8552 Typical Wiring for Current Input.
Specifications (Continued)
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 32 to 140°F (0 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Dimensions 4-1/4 H x 2-13/16 W x 2-5/32 D in. (108 x 71 x 55 mm)
Agency Listings
UL 873
Underwriters Laboratories (File #E9429 Category Temperature-Indicating and Regulating
Equipment.
CUL Canadian Standards C22.2 No. 24-93.
European Community EMC Directive (89/336/EEC). Emissions (EN50081-1). Immunity (EN61000-6-2).
General Instructions Refer to F-26159.
Model No. Description
AL-3x2 Pressure gauge.
K-335 In-line air filter.
B-371 Branch tee.
M-127 90° drop ear elbow.
M-636 4 in. T and B wire tie.
P-610 35 mm DIN rail (1-3/8 W x 36 L x 3/10 H in.)
+
–
3 to 15 psig
(21 to 103 kPa)
to controlled device
(direct acting)
+4 to 20 mA Current Input Signal
M
CP-8551
B
M
Signal Common
24H
M
CP-8552
B 3 to 15 psig
(21 to 103 kPa)
to controlled device
(direct acting)
Voltage Input Signal
Signal Common
+IVI
COM
M
24 Vac/dc
1
2
3
1
1
Power Common
When multiple CP-8552s or other
devices are powered by a common
source, uniform wiring polarity must be
maintained between all 24H and COM
terminals. Check to ensure that the
controller's COM terminal is not
connected to any other ground
reference.
M
CP-8552
B
3 to 15 psig
(21 to 103 kPa)
to controlled device
(direct acting)
Signal Common
+4 to 20 mA Current Input Signal
COM
M
1
2
3
+IV1