Accessory List
CP-8551, CP-8552
64
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Electronic to Pneumatic Transducer
Model Chart
Specifications
The CP-8551 and CP-8552 transducers receive a
variable electronic input signal and produce a
3 to 15 psig (21 to 103 kPa) pneumatic output signal to
position pneumatic damper and valve actuators in
HVAC systems.
Features:
• Durable enclosure with easily accessible wiring terminations.
• Panel or DIN rail mounting for quick, snap-on installation.
• Two-wire loop powered or three-wire voltage input.
• High accuracy with low hysteresis.
• Long-term driftless operation with high repeatability.
• Low air consumption and large air flow capacity.
• Control input protection from short circuit or reverse polarity.
Model No.
a
a
CAUTION: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-
isolated full-wave rectifier power supplies. Refer to EN206 F-26363.
Input Signal
Input Impedance
Ohms
Power Requirements
CP-8551 4 to 20 mA
550 maximum,
400 minimum
None
CP-8552
4 to 20 mA
550 maximum,
400 minimum,
4 to 20 mA input,
>10,000 Vac input
None
6 to 9 Vdc,
0 to 10 Vdc
20 to 30 Vac,
24 to 30 Vdc,
3.9 VA,
1.6 W
Input signal Refer to Model Chart.
Rectifier type Half wave, not isolated.
Input range adjustment
CP-8551: Fixed, 16 mAdc.
CP-8552: Jumper selectable. Refer to Model Chart.
Power supply
0 to 10 and 6 to 9 V: Requires 20 to 30 Vac, 3.9 VA (CP-8552), 50/60 Hz, or 24 to 30 Vdc power
supply, 1.6 watts maximum.
Air supply required
20 psig (138 kPa) nominal, 30 psig (207 kPa) maximum. Clean, dry, oil free air required (reference
EN-123, F-22516).
Air consumption for sizing air
compressor
Maximum 0.012 scfm (5.66 ml/s) at 20 psig (138 kPa) supply.
Air capacity for sizing air mains Minimum 550 scim (150.24 mL/s).
Air connections Male barbed fittings for flexible 1/4” O.D. pneumatic tubing.
Wiring connections Screw terminals for 16 to 22 AWG wire.
Output signal 3 to 15 psig (21 to 103 kPa) nominal, direct acting.
Adjustments
CP-8551: None.
CP-8552: 4 to 20 mA range, none; 0 to 10 and 6 to 9 V range, adjustable start point and span
potentiometers.
Maximum pneumatic output 1 to 18 psig (7 to 124 kPa).
Maximum air capacity 515 scim (141 ml/s) maximum with a 20 psig (138 kPa) supply.
Operating characteristics
Linearity ±1% of span at 75°F (24°C).
Hysteresis 0.75% of span at 75°F (24°C).
CP
-
8551
CP-855
2