Accessory List
CP-8511-xxx Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 63
Accessories
Typical Applications
Figure 1 Typical CP-8511 Wiring with Optional +20 Vdc Supply.
Specifications (Continued)
Air consumption for sizing air
compressor
Maximum 0.012 scfm (5.66 ml/s).
Air capacity for sizing air mains 550 scim (150.24 ml/s).
Air connections Male barbed fittings for flexible 1/4” O.D. pneumatic tubing.
Wiring connections Screw terminals for use with 16 to 22 AWG wire.
Outputs 3 to 15 psig (21 to 103 kPa).
Maximum pneumatic output 1 to 18 psig (7 to 124 kPa).
Action Refer to Model Chart.
Output air capacity & pressure 515 scim (141 mL/s) with a 20 psig (138 kPa) supply.
Operating characteristics
Linearity ±1% of span @ 75°F (24°C).
Hysteresis 0.75% of span @ 75°F (24°C).
Adjustments Field adjustable zero potentiometer.
Auxiliary power supply +20 Vdc @ 50 mA (maximum).
Auto/manual feedback Isolated open collector output transistor.
Auto/manual status Green LED.
Pressure gauge accuracy Within 2% of total scale range in middle portion of scale and 3% elsewhere (ANSI Class B).
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 32 to 140°F (0 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Mounting
Upright position. Unit is provided with section of plastic track for panel mounting. AD-8912 enclosure
can be ordered separately for remote installations.
Dimensions 4-1/4 H x 5 W x 2-5/32 D in. (108 x 127 x 55 mm).
Agency Listings
UL UL-873, Underwriters Laboratories.
European Community EMC Directive (89/336/EEC). Emissions (EN50081-1). Immunity (EN61000-6-2).
CSA Canadian Standards C22.2 No. 24-93.
General Instructions Refer to F-26205.
Model No. Description
K-335 In-line air filter.
P-610 35 mm DIN rail (1-3/8 W x 36 L x 3/10 H in.).
Optional
Control
Equipment
(Not Provided)
1
+20 V supply: 50 mA maximum
current output to drive other devices.
1
24H
M
CP-8511
B
Branch
24 Vac
50/60 Hz
24G
+20
M
2
COM terminal is internally connected to 24G. When
multiple CP-8511s or other devices are powered
by a common source, uniform wiring polarity must
be maintained between all 24H and 24G terminals.
Check to ensure that the controller's COM terminal is not
connected to any other ground reference.
COM
Typical
Controller
+IN
2