Accessory List

CP-8261-333, CP-8261-702
50
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Accessories
Typical Applications
Figure 1 CP-8261-xxx3-Heat/3-Cool/Mixed Air
(Showing Program as Shipped from Factory).
Relay Contact Ratings.
Volts AC 50/60 Hz Contact Va Rating Inrush VA
120/240
N.O. 125 1250
N.C. 67 670
24
N.O. 25 250
N.C. 13 130
Model No. Description
AD-8969-201 Offset resistor kit; 5, 10, 15, and 20°F.
AT-8122 Remote setpoint adjuster, dual scale 20 to 120°F (-6 to 49°C).
AT-8155 Remote setpoint adjuster, dual scale 50 to 250°F (10 to 120°C).
AT-8158 Remote setpoint adjuster, dual scale 55 to 85°F (13 to 29°C).
AT-8258-101 Night setback scale for AT-8158.
CP-8161-433 Slave.
TC-4111 Bulb thermostat.
THC-2 Enthalpy controller.
TS-8101 Room sensor.
TS-8131 Room button-type sensor.
TS-8201 Duct/immersion sensor.
TS-8261 Light fixture sensor.
TS-8405 Averaging sensor, 5 ft. (1.5 m).
TS-8422 Averaging sensor, 22 ft. (6.7 m).
TS-8501 Outdoor sensor.
TS-8601 Selective ratio discharge sensor.
TSP-8101-103 Temperature transmitter.
TOOL-201 Calibration kit for TAC System 8000.
1 For heat pump applications, use
relay #1 (J1 on 5.5 pin) to put
the changeover valve in the
heating mode. This allows 5
relays for 2 stages of heating
and 3 stages of cooling.
2 MP-371, -381, -471, -481, -2113
series using a CP-8301 solid
state drive, or MP-5400
hydraulic actuator.
3 Tape off.
4 Terminal 8 on TS-8101.
5 Terminal 7 on TS-8101.
6 MS4D-x0x3-130,
MS40-7043-MPx,
MS51-7103-30 w/AM-764,
MS51-7103-40 w/AM-764.
2
3
1
4
5
CP-8261-333
CP-8261-702
Mixed Air
Actuator
TS-8405
TS-8422
TS-8201
Mixed Air
Sensor
TS-8101
TS-8131
TS-8201
TS-8261
TS-8405
TS-8422
TS-8501
Main
Sensor
Black
Black
Black
Black
Yellow
Red
C2
NO2
NC1
C1
NO1
NC2
NO3
C3
C5
NO5
NO4
NC4
C4
NC3
NC5
NC6
NO6
C6
Heat
Stage 1
Heat
Stage 2
Heat
Stage 3
Cool
Stage 1
Cool
Stage 2
Cool
Stage 3
Proportional Heating
Pro
p
ortional Coolin
g
ISB
OP3
COM
+6.2
ISA
24G
24H
IO2
IO1
24 Vac
10 VA
50/60 Hz
Blue
6
Yel/Blk
Blk
Or
To OP3
To COM