Accessory List

CP-8261-333, CP-8261-702
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 49
Specifications
Sequenced control
Staged and/or proportional heating, proportional control of outside and return (mixed air) damper,
staged and/or proportional cooling. Heating and cooling cannot operate simultaneously.
Single Setpoint (SPB)
55 to 85°F (13 to 29°C). Heating, cooling, and ventilation are controlled from a single sensor and a
single setpoint.
Nullband Adjustment (SPA)
2 to 14°F (0 to 8°C); factory set at 3°F (2°C). Provides for separating the heating and
ventilation/cooling.
Mixed Air Low Limit Setpoint (SPC) 41 to 95°F (5 to 35°C).
Relay rating 24/120 Vac, 1 amp. 240 Vac, 0.5 amp inductive. Refer to the Relay Contact Ratings Model Chart.
Adjustments, minimum position
Minimum mixed air damper position (0 to 100%) factory set at 25%. For other adjustments refer to
the Description Model Chart and Proportional Outputs and Output Relays Model Chart.
Unit fan May be programmed to cycle in the unoccupied mode.
Relay output
Six relays can be programmed for heating, cooling, or fan operation. Operational voltage level by
dual-in-line switches.
Mixed air sensor (optional)
The controller can provide a separate mixed air control, or limit control in conjunction with
proportional cooling output ramp.
Cold start On power failure.
Control output voltage Refer to the Description Model Chart and Proportional Outputs and Output Relays Model Chart.
Power requirements 24 Vac, 10 VA.
Rectifier type Half wave, not isolated.
Power supplies available
6.2 Vdc, 4 mA; 20 Vdc, 35 mA. These regulated and filtered power supplies must not be connected
to +20, +6.2 or red lead of other supplies.
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 0 to 140°F (-18 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Connections Coded screw terminals.
Cover Aluminum.
Mounting Unit is provided with plastic track for panel mounting.
Dimensions 3-7/8 H x 12 W x 2-3/4 D in. (98 x 305 x 70 mm).
Agency Listing UL Recognized.
General Instructions Refer to F-23832.