Accessory List
CP-8161-333, CP-8161-433 (Slave)
46
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Specifications
Accessories
Relay Contact Ratings.
Volts AC 50/60 Hz Contact Va Rating Inrush VA
120/240
N.O. 125 1250
N.C. 67 670
24
N.O. 25 250
N.C. 13 130
Sequenced control
Staged and/or proportional heating, proportional control of outside and return (mixed air) damper,
staged and/or proportional cooling. Heating and cooling cannot operate simultaneously.
Single sensor control
Heating, cooling, and ventilation with individual heating and cooling setpoints.
Unit fan
May be programmed to cycle in the unoccupied mode.
Relay output
Six relays can be programmed for heating, cooling or fan operation. Operational voltage level by
dual-in-line switches.
Mixed air sensor (optional)
The controller can provide a separate mixed air control, or limit control in conjunction with
proportional cooling output ramp.
Cold start
On power failure.
Control output voltage
Refer to Description Model Chart and Mixed Air and /Relay Outputs Model Chart.
Power requirements
24 Vac, 10 VA.
Power supplies available
6.2 Vdc, 4 mA; 20 Vdc, 35 mA. These regulated and filtered power supplies must not be connected
to +20, +6.2 or red lead of other supplies.
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 0 to 140°F (-18 to 60°C).
Humidity
5 to 95% RH, non-condensing.
Locations
NEMA Type 1.
Connections
Coded screw terminals.
Cover
Aluminum.
Mounting
Unit is provided with plastic track for panel mounting.
Dimensions
3-7/8 H x 12 W x 2-3/4 D in. (98 x 305 x 70 mm).
Agency Listings
UL Recognized, CSA.
General Instructions Refer to F-18096.
Model No. Description
AD-8969-201 Offset resistor kit; 5, 10, 15, and 20°F.
AT-8122 Remote setpoint adjuster, dual scale 20 to 120°F (-6 to 49°C).
AT-8155 Remote setpoint adjuster, dual scale 50 to 250°F (10 to 120°C).
AT-8158 Remote setpoint adjuster, dual scale 55 to 85°F (13 to 29°C).
AT-8258-101 Night setback scale for AT-8158.
TC-4111 Bulb thermostat.
THC-2 Enthalpy controller.
TS-8101 Room sensor.
TS-8131 Room button-type sensor.
TS-8201 Duct/immersion sensor.
TS-8261 Light fixture sensor.
TS-8405 Averaging sensor, 5 ft. (1.5 m).
TS-8422 Averaging sensor, 22 ft. (6.7 m).
TS-8501 Outdoor sensor.
TS-8601 Selective ratio discharge sensor.
TSP-8101-103 Temperature transmitter.
TOOL-201 Calibration kit for TAC System 8000.