Accessory List
CP-8102, CP-8102-116
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 39
Typical Applications
Figure 1 Typical Temperature Control Wiring.
Jumper Connections.
Controller Function
Jumper Connections Required
Bridge “A” Bridge “B”
Direct acting
a
a
As supplied from factory.
J4 to JC6
J3 to JC5
J5 to JC5
J6 to JC6
Reverse acting
J4 to JC5
J3 to JC6
J5 to JC6
J6 to JC5
Internal setpoint active
a
J1 to JC1 J2 to JC3
Internal setpoint inactive for remote setpoint J1 to JC2 J2 to JC4
Disable Bridge “B” for single sensor input Remove jumper from AB2 to AB3
To
Controlled
Device
1
Optional
2
2
Remove jumper if no sensor is connected to ISB
ISA
ISA
AB2
AB3
ISB
ISB
OP1
COM
+20
+20
CP-8102
+20 (Red)
IV1 (Yellow)
COM (Blue)
1
1K
Sensing Element A
1K
Sensing Element B
TS-8000 Series