Accessory List

CP-8102, CP-8102-116
38
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Specifications (Continued)
Accessories
Typical controlled devices Maximum of six TAC System 8000.
CC-8100 Series relays.
MF-63123 Floating valve actuator.
MFC-8000 Control module card for MF-62123 actuator.
MM/MMR-400 Series Modular actuators w/MMC-8000 control module.
MM/MMR-500 Series Modular actuators w/MMC-8000 control module.
MP-300-600 Series Actuators.
MP-400-600 Series Actuators.
MP-5000 Series Actuators.
MS-1233 Series Damper actuators.
MS4D-x0x3-030 Actuators.
MS40-7043-MP Actuators.
MS40-7043-MP5 Actuators.
MS51-7103-030 Actuators.
MS51-7103-040 Actuators.
SP-40000 Series Step controllers.
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 40 to 135°F (4.4 to 57°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Connections Coded screw terminals for 14 to 20 AWG.
Cover Aluminum.
Mounting
Unit is provided with plastic track for panel mounting. AD-8912 enclosure can be ordered separately
for remote installations.
Dimensions 4 H x 11 W x 2-1/2 D in. (102 x 279 x 64 mm).
General Instructions Refer to F-14969.
Model No. Description
AD-8122 Signal adaptor for dual outputs (two direct acting).
AD-8123 Signal adaptor for dual outputs (one direct, one reverse acting).
AD-8124 Signal adaptor for dual outputs (one reverse, one direct acting).
AD-8912 Enclosure, 12 in. (305 mm).
AD-8969-201 Offset resistor kit: 5, 10, 15 and 20°F
AD-8969-901 Extended throttling range jumper.
AT-8122 Remote setpoint adjuster, dual scale 20 to 120°F (-6 to 49°C).
AT-8155 Remote setpoint adjuster dual scale 50 to 250°F (10 to 121°C).
AT-8158 Remote setpoint adjuster, dual scale 55 to 85°F (13 to 29°C).
AT-8222-101 Setpoint scale for humidity 20 to 100%.
AT-8435 Remote setpoint adjuster, dual scale 50 to 450°F (10 to 232°C) for use with TS-8204 only.
CN-8101 Multi-purpose bridge.
TOOL-201 Calibration kit forTAC System 8000.