Accessory List

CP-8102, CP-8102-116
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 37
TAC System 8000 Two-Input Temperature or Humidity
Controller
Model Chart
Specifications
This two-input temperature or humidity controller
provides heating, cooling, humidification, or
dehumidification control in HVAC systems.
Features:
Individual setpoints for each input element.
Self contained package incorporating two bridges and
amplifiers.
One input element has a 0.5 to 1 through 25:1 ratio
adjustment.
Accommodates all temperature/humidity TAC System
8000 devices.
Temperature setpoint ranges can be customized with
remote setpoint assemblies.
Standard TAC System 8000 track mounting.
Model No.
Control
Dial Range Setpoint “A”
Control
a
Dial Range Setpoint “B”
a
For reset control, set setpoint “B” at zero reset point and setpoint “A” at control point desired with no reset action from sensor “B”.
Throttling Range for 3 Vdc Output Change
CP-8102 20 to 120°F 20 to 120°F Adjustable 2 to 10 F° by dial
b
b
15, 25, 40, and 60°F by pin selection (use J9 jumper). With the use of AD-8969-901 (order separately), the following T.R.’s can be obtained: 55, 65, 75,
85, 100, 115, 125, and 140°F (13,18, 24, 29, 38, 46, 52, and 60°C).
CP-8102-116 -6 to 48°C-6 to 48°C Adjustable 1 to 6 C° by dial
b
Sensors
Temperature TS-8xxx one or two; three sensors through a CN-8101.
Humidity HS-8x01, VER-HDxx-MSx, VER-HOxx-MSx, VER-HxWx-MA.
Control action Direct (D.A.) or reverse (R.A.) selectable by jumper. Factory set D.A.
Authority ratio adjustment 0.5:1 to 25:1, adjustable by dial.
Control output voltage
1 to 15 Vdc, 10 mA maximum. Unit factory calibrated for 7.5 Vdc output with sensor at setpoint
temperature.
Power requirements 20 Vdc (-1.5, +1), 23 mA.
Power supply available
6.2 Vdc, 7 mA maximum. Regulated and filtered power supply must not be connected to +6.2 of
other supplies.
Remote setpoints Order separately AT-8122, AT-8155 or AT-8158.
Setpoints, ratio and throttling
potentiometers
Visible and accessible without removing controller cover.
P
-
8102
,
P
-8102-116
C
P-
8012-0-
1
C
P