Accessory List

CC-8118-120
32
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
TAC System 8000 Eight-Stage Sequencer Controller
Model Chart
Specifications
This controller is an electronic linear sequencer for
sequencing external low or line voltage contactors
or other loads. This unit also has a 2-15 Vdc
proportional output for use with other controlled
devices.
Features:
Dual sensing input capability.
2 to 15 volt control signal for additional functions.
Can be adapted to competitive 135 Ω controllers.
Power demand input for load shedding ability.
Proportioning output signal to afford proportional control
between on-off stages.
Self-contained UL/CSA approved wiring package.
Model No.
Power Requirements
Vac 11 VA
50/60 H
Staging
Stages Available by Multi-
Unit Operation
CC-8118-120 120 Linear eight stage heat or cool (“first on, last off”)
48 Parallel
24 Sequence
Sensors
Balco
1000 ohm single or dual sensor input. Three sensor input by the use of CN-8101 multipurpose
bridge.
Slidewire 135 ohm.
Inputs
Power demand 2 to 15 Vdc from a power monitor.
1 to 15 Vdc Unit operates at 2 to 5, 6 to 9, 10 to 13 Vdc.
Control dial range
Setpoints “A” and “B” 20 to 120°F (-6 to 49°C).
Action Direct, factory set, or reverse; change by pin selection.
Throttling range
Dial adjustable 2 to 10 F degrees (1.1 or 5.5 C degrees), factory set 3 F degrees (1.6 C degrees),
dual marked. 12 to 40 F degrees available by the addition of resistors.
Authority ratio Dial adjustable 0.5:1 to 25:1.
Staged sequencing relay outputs Eight SPDT has adjustable dropouts and selectable differential.
Linear (“first on”, “last off”)
Time delay between stages Standard 10 seconds, resistor selectable 5 to 60 seconds. Return to cold start on power interruption.
CC
-
8118
-
1