Accessory List
CC-8111-xxx Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 31
Typical Applications
Figure 1 Discharge Temperature Control with Outdoor Air Reset.
Figure 2 Tank Differential Temperature Control.
Single Input.
Input
Bridge and
Input Action
Internal Connections Sensor Connection
A
Direct acting J1 to COM, J2 disconnect and tape ISA and +6.2
Reverse acting J1 to +6.2, J2 disconnect and tape ISA and COM
Dual Input.
Input A Action Sensor A Between J1 to Pin
Reset Action of Input
B
J2 to Pin
Sensor B
Between
Direct acting
a
a
Factory set.
+6.2 and ISA COM
Direct reset
a
+6.2 ISB-COM
Reverse reset COM ISB-+6.2
Reverse acting ISA and COM +6.2
Direct reset COM ISB-+6.2
Reverse reset +6.2 ISB-COM
5 Additional TAC System
8000 Controlled Devices
IV1
OP1
+6.2
ISA
AB1
ISB
COM
L1
L2
NC1
C1
NO1
CC-8111-120
Controlled
Device
120 Vac 50/60 Hz
(Blue) Com
(Yellow) IV1
Outside
Air
TS-8501
Sensor B
GRND
+20
Optional
Discharge
Air Sensor
TS-8201
Sensor A
Note: 2 to 15 Vdc D.A.Signal.
IV1
OP1
+6.2
ISA
AB1
ISB
COM
L1
L2
NC1
C1
NO1
CC-8111-120
Controlled
Device
i.e. Pump
120 Vac 50/60 Hz
Tank 2
TS-8201
Sensor B
GRND
+20
Tank 1
TS-8201
Sensor A
Note: For temperatures between
250 and 450˚F, use TS-8204.