Accessory List
CC-810X Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 25
TAC System 8000 Controlled Relays
Model Chart
Specifications
Electronic controlled relays are offered in dual, or
dual with one having heat anticipation for time
proportional control of electric heat.
Features:
• Stages individually adjustable.
• Large selection of operational differentials available.
• Uses standard track mounting.
• Can accommodate two individual inputs.
Model No.
Input
Signals
Description
Power
Requirements
Vac (50/60 Hz)
(+10/-15%)
Relay
Relay 1
Dropout
Deadband
(Differential)
Pull-in
Relay 2
(CC-8103 Only)
Time Proportioning
CC-8102
1 or 2
2 relays
120 Adjustable 2
to 12 Vdc
(input
signal);
factory set 6
Vdc
Jumper
selectable 1/2,
1, 2, 4 Vdc
a
(input signal);
factory set
1 Vdc
a
1.5, 2.5, 3, 3.5, 4.5, 5, 5.5, 6, 6.5, 7, 7.5 Vdc differentials can be obtained with an AD-8969-901 (order separately).
Pull-in equals
dropout plus
deadband
Adjustable 2 to 12
Vdc (input signal)
factory set to drop out
at 8 Vdc
CC-8102-024
b
b
Not CSA certified.
24
CC-8103
2 relays,
1 time
proportioning
120
Adjustable 2
to 12 Vdc
(input
signal);
factory set
10 Vdc
Non-adjustable
6 VDC input: 1
00% duty cycle
7.5 Vdc input:
50% duty cycle
9 Vdc input:
0% duty cycle
CC-8103-240 240
Input signals One or two 2 to 15 Vdc input signals.
Relay SPDT. Refer to Electrical Rating per Relay Table for electrical ratings.
Power requirements Refer to Model Chart.
Power consumption 2.4 VA.
Power supply available 20 Vdc, 35 mA; filtered and regulated.
Environment
Ambient temperature limits
Shipping and storage: -40 to 140°F (-40 to 60°C).
Operating: 40 to 135°F (4 to 57°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Connections Coded screw terminals for 12 to 20 AWG.
Cover Aluminum.
Mounting
Unit is provided with plastic track for panel mounting. AD-8912 enclosure can be ordered separately
for remote installations.
Dimensions 3-7/8 H x 7-1/2 W x 2-1/2 D in. (98 x 191 x 63).
Agency Listings
CC-8102 and CC-8103: UL Recognized CSA.
CC-8102-024: UL Recognized.
General Instructions Refer to F-14966.
C
-
810X
r
ies