Accessory List
Accessories and Tools
356
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Application
Package of 100 dial stop pins to insert in dial ends to limit the
high or low setting of room thermostats.
Specifications
• Electric.
- All except TA-121, TC-114.
• Electronic.
- TP-810x.
- TP-8232.
- TS-5191.
- TS-5711.
- TS-811x.
• Pneumatic.
- All TK-1xxx and TK-5xxx except TK-17xx, TK-18XX.
AT-104
Dial Stop Pins
Application
Immersion well for use with 3/8 in. (10 mm) temperature bulbs.
Specifications
• Ambient temperature limits: -40 to 350°F (-40 to 177°C).
• Refer to F-18895 for complete applications.
AT-201, AT-203, AT-206
Immersion Well
Model No. Material
Dimensions
Application Limitations at
250°F (121°C) Fluid Temp.
Used With
O.D.
in.
(mm)
Insertion
Probe
O.D.
Max.
Insertion
Length
in. (mm)
Overall Well
Length
in. (mm)
Internal
Fitting
Thread
External
Fitting
in.
Max.
Recom.
Velocity
FPS (m/s)
Max. Recom.
Static
Pressure
psig (kPa)
AT-201
a
Copper
1/2
(13)
b
.3750
9-1/2
(241)
10-1/4
(260)
5/8-18
3/4
MNPT
11
(3.3)
250
(1728)
TC-28x,
TC-4x1x,
TC-4x2x,
TC-4x5x,
TK-6024,
TK-6124,
TKS-8000’s
AT-203
a
Stainless
Steel
1/2
(13)
b
.395
9-1/2
(241)
10-1/2
(267)
3/4
MNPT
20
(6.1)
500
(3448)
Same as
AT-201
AT-206 Copper
1/2
(13)
b
.420
4-1/2
(114)
5-13/16
(148)
—
1/2
MNPT
11
(3.3)
250
(1728)
TC-4x1x,
TC-4x2x,
TC-4x5x,
TK-6024,
TK-6124
a
Requires AT-209 for TC-4x1x, TC-4x2x, TC-4x5x, TK-6024, TK-6124.
b
For 3/8 in. (10 mm) diameter bulbs.