Accessory List
Accessories and Tools
330
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Application
Single potentiometer for use in position indicating
applications or in paralleling actuators. For use with MP
oil-submerged gear train actuator or AM-348 mounting
bracket.
Specifications
• Construction: Spring-loaded friction-driven copper wiper arm
with a contact that rides on a uniformly wound wire resistance
card.
• Resistance card:
- Resistance: 100 Ω; use with a power supply not to exceed
25 Vac.
- Electrical capacity: 3 watts.
• Connections: Coded screw terminals.
• Case: Aluminum. 1/2 in. conduit knockouts on right and left hand
sides.
• Mounting: To back of actuator, or AM-348.
• Dimensions: 4-3/16 H x 4 W x 2 D in. (106 x 102 x 51 mm).
• May be used with: AE-504 Paralleling relay (required for
paralleling applications).
• Refer to F-09240 for complete applications.
Note: If installed on NEMA4 actuator the assembly will no longer be
NEMA4.
AM-332
Potentiometer
Application
Auxiliary four-step switches for multiple step control of
compressors, pumps, auxiliary control of relays, indicating
circuits and similar applications. Use with MC and MP oil-
submerged gear train actuators or AM-348 mounting bracket.
Specifications
• Electrical switch: Four snap-action SPDT. Setting of each switch
is adjustable using the wrench included. Differential of each
switch is adjustable (minimum differential is 9°).
- Ratings: Refer to table.
• Connections: Coded screw terminals.
• Case: Aluminum. 1/2 in. conduit knockouts on right and left hand
sides.
• Mounting: To back of actuator, or AM-348.
• Dimensions: 4-3/16 H x 4 W x 3-7/16 D in. (106 x 102 x 87 mm).
• Refer to F-09240 for complete applications.
Note: If installed on NEMA4 actuator the assembly will no longer be
NEMA4.
AM-341
Auxiliary Four-Step Switch
Full Load Amps Locked Rotor Amps Non-Inductive Amps
Max. Total Load
Not to Exceed
120 Vac 240 Vac 120 Vac 240 Vac 120 Vac 240 Vac
5.8 2.9 34.8 17.4 15 7.5 2000 VA