Accessory List
Accessories and Tools
328
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Application
For connecting MM and MMR-400/500 Series modular
actuators to 120, 208, or 240 Vac power sources.
Specifications
• Power supply:
- Primary: 120/208/240 Vac (+10, -15%), 50/60 Hz. For
maximum reliability and operating life, use at nominal primary
voltage.
- Secondary: 24 Vac.
-VA: 40.
• Ambient temperature limits:
- Shipping and storage: -40 to 160°F (-40 to 71°C).
- Operating: -40 to 130°F (-40 to 54°C).
• Humidity: 5 to 95% RH, non-condensing.
• Locations: NEMA Type 1 (NEMA 3R with AM-232 gasket kit
installed on modular actuator).
• Connections:
- Primary: 8 in. (203 mm) color coded pigtail leads.
- Secondary: 8 in. (203 mm) brown pigtail leads with 1/4 in.
quick-connect (spade lug) terminals.
- Housing: Glass-reinforced thermoplastic (PET). UL-94-5V
flame-rated housing material to meet UL-465 requirements for
air plenum mounting.
- Mounting: To top of modular actuator housing. Four screws
provided to secure kit to modular motor housing. Weather
resistant cover gasket kit included.
- Dimensions: 1-15/16 H x 5-11/16 W x 4 D in.
(49x144x102mm).
• Refer to F-23353 for complete applications.
AM-231
Transformer/Cover Kit
(if power 120, 208, or 240 Vac)
Application
For providing a replacement NEMA 3R weather resistant kit for
MM and MMR-400/500 Series modular actuators.
Specifications
• Kit contains:
- One top cover gasket.
- One internal switch cover gasket.
• Gasket material: 1/16 in. (1.6 mm) thick closed cell Neoprene.
• Mounting: Modular housing must be mounted vertically
⎯ top up ⎯ and weather resistant conduit connectors are
required for NEMA 3R rating.
• Dimensions:
- Top cover gasket: 5-1/2 x 3-13/16 in. (140 x 97 mm).
- Internal switch cover gaskets: 3-5/8 x 1-21/32 in.
(92 x 42 mm).
• Refer to F-23481 for complete applications.
AM-232
Replacement Weather Resistant Kit