Accessory List
VER-PxP Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 309
Specifications
Accessories
Typical Applications
Figure 1 Typical Wiring for VER-PxP Series, Three Wire Vdc Output.
Figure 2 Typical Wiring for VER-PxP Series, Two-Wire mA Output.
Inputs
Media compatible Clean dry air or any inert gas.
Load impedance capability 600 ohm minimum.
Proof pressure 3 PSID. Burst 5 PSID.
Operating characteristics Accuracy: ± 1% FS includes: linearity, hysteresis, and repeatability.
Air consumption None.
Connections 1/8 inch brass hose barb fitting air connections. Cage clamp terminal block electrical connections.
Outputs
Electrical
Signal 4 to 20 mA, 2-wire. 0 to 5 Vdc or 0 to 10 Vdc, 3-wire.
Supply voltage 24 Vac/dc nominal ±15%. 9 mA draw (AC), 4 mA draw (DC).
DC power supply rectifier type Half-wave. (Refer to previous Caution). EN206. F-26363.
Environment
Ambient temperature limits
Shipping and handling: -32 to 140°F (0 to 60°C).
Operating: 32 to 140°F (0 to 60°C).
Humidity 10 to 90%, non-condensing.
Location Plenum rated UL 94. Meets UL94 VO.
Dimensions 4.49 H x 3.3 W x 2.14 D in. (114 x 84 x 54 mm).
Model No. Description
N1-5x Differential pressure pickups (series).
-
+
Power Source
24Vac/DC
-
Controller
VER-PxP
0 to 10 V
COM
Power
Out
-
+
Power Source
24Vdc only
-
Controller
VER-PxP
4 - 20 mA
COM
Power