Accessory List

VER-PxP Series
308
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Static & Differential Pressure Transducer
Model Chart
The VER-PxP Series Static and Differential
Pressure Transducer is used to monitor and
control building static pressure, air flow, and filter
pressure drop. Microprocessor based for
increased accuracy and reliability.
Features:
±1% accuracy (including linearity, hysteresis, and
repeatability).
Advanced ceramic capacitance sensor.
As low as 0.1” W.C.
Up to three PSID overpressure without zero shift.
Up to sixteen field selectable rangesover two models.
Field selectable output versions, 4 to 20 mA two-wire or
three-wire 0 to 5 Vdc/0 to 10 Vdc.
Short circuit and reverse polarity protected.
Conforms to EMC standards EN50082-1/
EN55014/EN60730-1.
24 Vac/DC nominal supply voltage.
Optional display.
Model No.
a
a
CAUTION: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-
isolated full-wave rectifier power supplies.
Range (in. W.C.)
b
b
Ranges may be unidirectional, as shown above, or bidirectional. Field selectable.
Input Supply Output Supply LCD Display
VER-PxPxx-01S
0 to 0.1/0 to .25/0 to 0.5/0 to 1.0
24 Vac/dc
nominal ±15%
2-wire, loop powered 4 to 20
mA or 3-wire 0 to 5 V/0 to 10 V
No
VER-PxPLx-01S Yes
VER-PxPxx-02S
0 to 1.0/0 to 2.5/0 to 5.0/0 to 10
No
VER-PxPLx-02S Yes