Accessory List
VER-PxP Series
308
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Static & Differential Pressure Transducer
Model Chart
The VER-PxP Series Static and Differential
Pressure Transducer is used to monitor and
control building static pressure, air flow, and filter
pressure drop. Microprocessor based for
increased accuracy and reliability.
Features:
• ±1% accuracy (including linearity, hysteresis, and
repeatability).
• Advanced ceramic capacitance sensor.
• As low as 0.1” W.C.
• Up to three PSID overpressure without zero shift.
• Up to sixteen field selectable rangesover two models.
• Field selectable output versions, 4 to 20 mA two-wire or
three-wire 0 to 5 Vdc/0 to 10 Vdc.
• Short circuit and reverse polarity protected.
• Conforms to EMC standards EN50082-1/
EN55014/EN60730-1.
• 24 Vac/DC nominal supply voltage.
• Optional display.
Model No.
a
a
CAUTION: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-
isolated full-wave rectifier power supplies.
Range (in. W.C.)
b
b
Ranges may be unidirectional, as shown above, or bidirectional. Field selectable.
Input Supply Output Supply LCD Display
VER-PxPxx-01S
0 to 0.1/0 to .25/0 to 0.5/0 to 1.0
24 Vac/dc
nominal ±15%
2-wire, loop powered 4 to 20
mA or 3-wire 0 to 5 V/0 to 10 V
No
VER-PxPLx-01S Yes
VER-PxPxx-02S
0 to 1.0/0 to 2.5/0 to 5.0/0 to 10
No
VER-PxPLx-02S Yes
VER-
PxP
Series