Accessory List
VER-PxD Series
306
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Duct Pressure Transducer
Model Chart
Specifications
The VER-PxD Series Duct Pressure Transducer is
used to monitor and control building static
pressure and duct static pressure. Microprocessor
based for high accuracy and reliability.
Features:
• ± 1% accuracy (including linearity, hysteresis, and
repeatability).
• Advanced ceramic capacitance sensor.
• Duct pressure transducer and static pressure tip integrated
as one unit.
• Up to three PSID overpressure without zero shift.
• Up to four field selectable ranges available in a single unit.
• 24 Vac/dc nominal supply voltage.
• Short circuit and reverse polarity protected.
• Conforms to EMC standards EN50082-1/
EN55014/EN60730-1.
• LCD display models.
Model No.
a
a
CAUTION: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-
isolated full-wave rectifier power supplies.
Range (inches WC)
b
b
Ranges may be unidirectional. as shown, or bidirectional field selectable.
Input Supply Output Supply Display
VER-PxDxx-015 0 to .1 / 0 to .25 / 0 to -5 / 0 to 1.0
24 Vac/dc nominal
Field selectable, 3-wire
(0 to 5 Vdc or
0 to 10 Vdc)
2-wire loop mA (4 to 20
mA)
No
VER-PxDxx-025 0 to 1.0 / 0 to 2.5 / 0 to 5.0 / 0 to 10
VER-PxDLx-01S 0 to .1 / 0 to .25 / 0 to .5 / 0 to 1.0
Yes
VER-PxDLx-02S 0 to 1.0 / 0 to 2.5 / 0 to 5.0 / 0 to 10.0
Inputs
Media compatible Clean dry air or any inert gas.
Load impedance capability 600 ohm minimum.
Proof pressure 3 PSID. Burst pressure 5 psid.
Operating characteristics Accuracy: ± 1% FS (included linerarity and hysteresis).
Outputs
Electrical
Signal 4 to 20 mA, 2-wire. 0 to 5 Vdc or 0 to 10 Vdc, 3-wire.
Supply voltage 24 Vac/dc nominal. ±15%. 9 mA draw (AC), 4 mA draw (DC).
DC power supply rectifier type Half-wave. (Refer to previous Caution). EN206. F-26363.
Connections Cage clamp terminal block.
Environment
Ambient temperature limits
Shipping and handling: -30 to 140°F (0 to 60°C).
Operating: 32 to 140°F (0 to 60°C).
Humidity 10 to 90%, non-condensing.
Location Meets UL 94 VO.
Dimensions 4.49 H x 3.3 W x 2.136 D in. probe (114 x 84 x 54 mm) 7.938 in. ( 202 mm).
Agency Listings
Conformance: EMC EN 50081-1, EN 50082-1, EN 61000-4-4, EN 61000-4-5, EN 61000-4-3,
ENV 50402, EN 61000-4-6.
VER
-
P
x
D
Series