Accessory List
TS-8811, TS-8811-116
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 291
Specifications
Accessories
Typical Applications
Figure 3 Sensor Wiring.
Sensing element
Temperature sensitive Balco element. 1000 Ω ±0.1% at 70°F (21°C); changes 2.2 Ω per 1°F (0.5°C)
at 70°F (21°C).
Remote setpoint dial range 55 to 85°F or 13 to 29°C, with resistance change equal to sensor resistance change.
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 40 to 140°F (4 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Connections Coded screw terminals.
Cover Beige plastic.
Mounting Wall.
Dimensions 4-3/8 H x 2-3/4 W x 1-5/8 D in. (111 x 70 x 43 mm).
General Instructions Refer to F-23849.
Model No. Description
AT-61 Series Brushed bronze cover plates.
AT-101 Lock cover kit.
AT-104 Dial stop pins.
AT-504 Plaster hole cover kit (small).
AT-505 Surface mounting base.
AT-546 Auxiliary mounting plate.
AT-602 Selector switch sub-base DP4T.
AT-1103 Wire guard.
AT-1104 Cast aluminum guard.
AT-1155 Plastic guard, 6-1/4 H x 5-1/2 W x 3-1/4 D in.
AT-1165 Plastic guard, 8 H x 5-1/2 W x 3-1/2 D in.
TS-8811-xxx
6P
7
8
To EMS Controller
Remote Setpoint Input
To EMS Sensor Input
1
C
1
C
1
P
1
1 CAUTION: For proper operation of EMS controller,
the polarity of the Point (P) and Common (C)
terminals of the TS-8811 must be observed.