Accessory List

TP-8232, TP-8232-xxx Series
274
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Room/Discharge Low Limit Temperature Controller
Model Chart
Specifications
These electronic room and low limit supply air
temperature controllers are used in heating
and air conditioning systems.
Features:
Low cost replacement for unit vent packages.
TAC System 8000 compatible for control functions.
Individual supply air setpoint with concealed adjustments
eliminate occupant tampering.
Day/night input capability.
Remote setpoint input.
Model No.
Setpoint Dials
Throttling Range
a
Adjustments
a
Throttling range (T.R.) is defined as °F (°C) change at the temperature sensor in order to cause a 6 to 9 Vdc controller output signal change.
Room
Supply
b
b
Units marked setpoints °F (°C).
Room
Supply
c
c
F marked setpoints only; 1 to 9°F (1 to 5°C).
TP-8232 55 to 85°F 45 to 75°F (7 to 24°C)
1 to 9°F 1 to 9°F
TP-8232-116
13 to 29°
C
7 to 24°C (45 to 75°F)
Construction Self-contained room controller with a 1000 Ω Balco sensing element.
Control dial range Refer to Model Chart.
Throttling range Refer to Model Chart.
Power requirements 20, (+1, -1.5) Vdc; 25 mA.
Output voltage 2 to 15 Vdc, direct acting only.
Power supply available 6.2 Vdc, 4 mA max.
Controlled devices Maximum of six TAC System 8000 (10 mA maximum).
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: 40 to 140°F (4.4 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1.
Connections Coded screw terminals and color coded wire leads.
Cover Beige colored plastic.
Mounting Wall. Panel, order AD-8951 mounting assembly.
Dimensions 4-3/8 H x 2-7/8 W x 1-5/8 D in. (111 x 73 x 41 mm).
General Instructions Refer to F-19057.
TP
-
8232
TP-8232
xx Seri
e
90
80
70
60
50
TP-8232