Accessory List

TP-8101, TP-8102, TP-8121, TP-8124
270
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Single/Dual Output Room Temperature Controllers
Model Chart
These temperature controllers are used in heating
and air conditioning systems.
Features:
Dual output adapters for TP-8101 and TP-8102.
TP-8124 meets ASHRA 90-75 DOE requirements.
Heating and cooling cannot operate simultaneously.
Heating/cooling deadband obtained by adjustable dual
setpoints and throttling range.
Concealed adjustments to eliminate occupant tampering.
Model No.
Control Dial Range
Description
Throttling Range
for 3 Vdc Output
Change
Power
Requirements
Output Voltage
Temp. Null-band
TP-8101 55 to 85°F
Single setpoint with
single output signal
room controller
2, 3, 6 and 20 F°;
factory set 3 F° by
jumper/pins
20 Vdc
(-1.5/+1) 13mA
2 to 15 Vdc or 15
to 2 Vdc
a
a
Units factory calibrated for 7.5 Vdc output with sensor at setpoint temperature providing a 6 to 9 Vdc output signal over the selected throttling range..
TP-8101-116 13 to 29°C
TP-8102 45 to 75°F
TP-8102-116 17 to 24°C
TP-8121 55 to 85°F
2 to 14°F
(1.1 to 8°C);
factory set at
3 (1.7)
Single setpoint with dual
output signal room
controller
Heating & cooling
2 to 10 F°,
independently adj;
factory set 3 F°
20 Vdc
(-1.5/-1) 23 mA
Heat (OP1) 2 to
15 Vdc or
15 to 2 Vdc
b
;
cool (OP2) 2 to
15 Vdc
b
Units factory calibrated for 6 Vdc (R.A. HTG), 9 Vdc (D.A. HTG) and 6 Vdc (D.A. CLG) with sensor at setpoint temperature.
TP-8124
TP-8124-770
Dual Scale
Heating
45 to 75°F
Cooling
70 to 100°F
Difference
between
heating &
cooling
setpoints
Dual setpoints and dual
output signals with
deadband between
heating and cooling
room controller
Power Supply, Wiring, Control Action, and Number of Controlled Devices.
Model No. Power Supply Wiring
Control
Action
Number of
Controlled Devices
TP-8101
6.2 Vdc 2.2 mA
max.
Three color coded pigtail leads,
terminals; for options refer to
Figure 4.
Factory set direct acting jumper
terminal 4 to 5; for reverse acting
jumper terminal 4 to 3
Six TAC System 8000 devices or
two MP-5200 series actuators
TP-8101-116
TP-8102
TP-8102-116
TP-8121
Coded terminals; refer to Figure
5 and Figure 6.
Heating factory set reverse
acting, jumper J7 to pin B for
direct acting; cooling direct acting
only
Six TAC System 8000 devices or
two MP-5200 series actuators in
both heating and cooling
TP-8124
TP-8124-770
TP
-
8101
,
TP-8102,
TP-8121,
TP-8124
90
80
70
60
50
TP-810X
TP-8121
TP-8124
TP-810X