Accessory List
TC-97 Series, TC-98 Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 247
Specifications
Accessories
Control Range
Heating 38 to 88
°F (5 to 30°C).
Cooling 60 to 108
°F (16 to 40°C).
Minimum Deadband 2 F degrees (1 C degree) between heating and cooling.
Shipping and Storage Temperature -40 to 124
°F (-40 to 48°C).
Operating Temperature 28 to 124
°F (0 to 48°C).
Humidity 5 to 85% RH, non-condensing.
Wiring Terminals Terminal block in wall plate. AWG #14 maximum.
Power Supply 24 Vac nominal 20 to 30 Vac, 50/60 Hz.
Relay Outputs Form A (SPST, normally open) relay commons are internally connected.
AC Rating 0.05 to 0.75 amp (continuous) at 24 Vac.
DC Rating 0 to 0.75 amp (continuous) at 24 Vdc.
Display
Range
Room Temperature Input 28 to 124
°F (0 to 48°C).
Outdoor Air Temperature
Measurement
-40 to 124
°F (-40 to 48°C).
Units
°F or °C.
Control Accuracy ±1 F degree at 68
°F (±0.5 C degrees at 20°C).
Mounting Flush.
Locations NEMA Type 1.
General Instructions
TC97-SHP: Refer to F-26403.
TC97-M: Refer to F-26404.
TC97-MHP: Refer to F-26405.
TC98-xxx: Refer to F-26406.
Model No. Description
WXU-10-528 Indoor air sensor (Robertshaw labeled)
WXU-10-529 Outdoor air sensor.
WXU-10-546 Add-A-Wire (allows 5-wire thermostats to be connected to 4-wire).