Accessory List

TA-3432, TA-3433, TA-3434, TA-3441
244
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
High/Low Temperature Thermostats
Model Chart
Specifications
For line voltage on-off control of media
temperatures in ducts, tanks, liquid lines, pipes,
etc.
Features:
Dual marked °F and °C scale.
5 and 10F degrees differential.
Locking screw standard.
Agency approval.
Manual reset standard.
Model No. Device Type
Functional Setpoint Dial
Range °F (°C)
a
a
Units dual marked °F and °C.
Differential
°F (°C)
Switch Type
TA-3432
High temp manual reset
75 to 135
(23 to 57)
Fixed
b
10 (5)
b
Reset cannot be accomplished until the sensed temperature is at least 5°F (3°C) below setpoint.
SPST opens on temp
rise
TA-3433
100 to 160
(38 to 71)
Fixed
b
5 (3)
TA-3434
120 to 240
(49 to 116)
Fixed
b
10 (5)
TA-3441 Low temp manual reset
35 to 59
(1.7 to 15)
Fixed
c
5 (2)
c
Reset cannot be accomplished until the sensed temperature is at least 5°F (3°C) above setpoint.
Note: Bulb well required for liquid service.
SPST opens on temp
drop
Setpoint dial range Refer to Model Chart.
Sensing element Helical bimetal.
Differential Refer to Model Chart.
Environment
Ambient temperature limits Shipping and operating: 100°F (55°C) above or below dial range.
Locations NEMA Type 1.
Electrical switch Refer to Model Chart.
Voltage 120 and 240 Vac.
Current
Full Load 16 Amps at 120 Vac, 8 Amps at 240 Vac.
Locked Rotor 96 Amps at 120 Vac, 48 Amps at 240 Vac.
Pilot Duty 720 VA.
Connections Coded terminals.
Cover Beige painted steel case with 1/2 in. conduit opening.
Mounting
In any position on any surface not subject to excessive vibration. For immersion mounting, bulb well
is required.
Dimensions
Case 5-3/8 H x 3-1/2 W x 1-7/8 D in. (136 x 89 x 48 mm).
Element 1/2 D x 7-1/2 insertion length, overall length 9-3/8 in. (131 x 191 x 238 mm).
Agency Listing UL, CUL.
General Instructions
Refer to F-11302.
TA
-
3432
TA-343
3
TA-343
4
TA-3441