Accessory List
TA-168 Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 237
Specifications
Accessories
Outputs.
Fan Switch Rating, Terminals 1 - 4 Control Output
Voltage
Inductive
Resistive Amps Pilot Duty
Terminals 7, 12,
13, and 14
FLA LRA
24 N/A N/A N/A 24 VA 10 VA
120 5.8 34.8 6.0 125 VA
N/A240 2.9 17.4 5.0 125 VA
277 2.4 14.4 4.2 125 VA
Inputs
Power input 20 to 28 Vac, nominal 24 Vac. Full wave device.
Power Consumption 25 mA maximum at 24 Vac.
Outputs
Electrical
Demand and aux. heat: 10 VA @ 24 Vac.
Electrical connections: Terminal strip with screw-down terminals.
Control signals 0 to 10 Vdc 1000 Ω minimum. 4 to 20 mA 100 - 600 Ω.
Control ranges
Setpoint adjustment range: 50 to 90°F (10 to 32°C)
Display range: 32 to 99°F (0 to 37°C).
Proportional band: 2 F degrees (1.1 C degrees).
Changeover deadband: 3 F degrees (1.6 C degrees)
Mechanical
Material: Rigid vinyl.
Finish: Cool gray.
Environment
Ambient temperature limits
Shipping and storage: -30 to 130°F (-34 to 55°C).
Operating: 32 to 130°F (0 to 55°C).
Humidity Maximum 95% non-condensing.
Locations NEMA Type 1.
Dimensions 2-3/4 H x 4-1/2 W x 1-1/8 D inches (79 x 114 x 28 mm).
Agency Listings UL Recognized, CE compliant.
General Instructions Refer to F-27025.
Model No. Description.
680-243-5 36” Changeover switch with clamp.
680-234-6 36” Changeover switch with conduit connector.
65345 4-3/4 x 4-3/4” adapter plate.
65821 Blank cover.
68671 Remote changeover sensor, 60 in. leads 10K
Ω @77°F (25°C).