Accessory List

TA-158 Series, TB-158 Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 229
TAC Erie™ Digital, 3-Wire Floating Thermostat/Controller
Model Chart
The T158 series microprocessor based
thermostat/controller with digital display provides
3-wire floating, on/off control, or a combination of
3-wire floating and on/off control. This series
controls a variety of two-pipe and four-pipe fan coil
units, air handling units, and various heating and
cooling applications.
The microprocessor combines a proportional plus
intergral control algorithm with advanced adaptive
logic. This provides control without the need for
tuning or calibration the control algorithm in the
field.
Features:
Heating and cooling outputs are individually configurable
for 3-wire floating or on/off control in the normally open or
normally closed modes.
Line voltage continuous 3-speed fan control.
Manual or automatic changeover.
Remote setback capability from a time clock or facility
management system.
Time out feature. Drive signal stops after 3 mins (max) on.
Fahrenheit or Celsius display capability.
Built-in purge cycle assists the controller to determine if the
controlling agent is providing heating or cooling.
Microprocessor eliminates the necessity for tuning or
calibration.
Display can be calibrated to within ±5F degrees (2.5C
degrees).
Model No.
abc
a
Do not use with actuators in which the motor is driven by DC voltage.
b
Do not use with actuators which have position memory on power loss.
c
Actuator must full stroke open or closed in 1 to 3 minutes.
Heat/Cool
Outputs
Control Signal
Options
Fan Control
d
d
Fan "Off" disables unit including display.
Demand
Output
Remote
Sensor
e
e
Remote sensor ordered separately.
Setback System Switches
TA-158-1 Dual 6 None
Yes
Yes Yes Off-Auto-Heat-Cool
TA-158-2 Dual 6 Off-Hi-Med-Lo Yes Yes Off-Auto-Heat-Cool
TB-158-1 Dual 1, 2, 3, 5, 6 None
Available
Yes Yes Off-Auto-Heat-Cool
TB-158-2 Dual 1, 2, 3, 4, 5, 6 Off-Hi-Med-Lo Yes Yes Off-Auto-Heat-Cool
TB-158-3 Single 5 Off-Hi-Med-Lo
No
Yes Yes Off-Heat/Off-Cool
TB-158-7 Single 5 None Yes Yes None
TB-158-15 Single 5 None Yes Yes Off-Heat/Off-Cool
TB-158-17 Dual 1, 2, 3, 4, 5, 6 Off/On
Available
Yes Yes Off-Auto-Heat-Cool
TB-158-18 Single 5 On/Off Yes Yes Off-Heat/Off-Cool
1. 3-wire floating single stage cooling and 3-wire floating single stage heating.
2. 3-wire floating cooling and two stage on/off heating.
3. Single stage on/off cooling, on/off fan control, and 3-wire floating single stage heating.
4. On/off single stage cooling, on/off single stage heating and fan control.
5. 3-wire floating single stage cooling or single stage heating.
6. On/off single stage cooling, on/off single stage heating.
-158
r
ies, TB-
8
Series