Accessory List

PP-8311 Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 207
Pressure Transducer
Model Chart
Specifications
This transducer converts a 3 to 15 psig
(21 to 103 kPa) or a 0 to 20 psig (0 to 137 kPa)
pneumatic input signal to a proportional
4 to 20 mAdc or 1 to 5 Vdc electronic output signal.
Features:
4 to 20 mAdc load capability to 625 Ω maximum.
Dual outputs for 4 to 20 mAdc and 1 to 5 Vdc.
3 to 15 psig factory calibrated.
Does not consume any air.
Can be calibrated for 0 to 20 psig.
Requires less panel spaces than former model.
Model No.
a
a
CAUTION: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-
isolated full-wave rectifier power supplies.
Transducer Power Input
Voltage Hz VA
PP-8311-024-0-0-1 24 Vac (±15%)
50 60
2.5
PP-8311-120-0-0-1 120 Vac (+10/-15%) 4.0
Inputs
Signal
Factory setting: 3 to 15 psig (21 to 103 kPa).
Adjustable to: 0 to 20 psig (0 to 137 kPa) by recalibration.
Load impedance capability 4 to 20 mA output 625 Ω maximum 1 to 5 volts output, 1,000 Ω minimum.
Maximum supply air pressure 30 psig (207 kPa).
Operating characteristics
Linearity: ±0.75% of span.
Hysteresis: ±0.25% of span.
Air consumption None.
Connections Coded screw terminals and one barbed fitting for 1/4 in. O.D. plastic tubing.
Outputs
Electrical
Output signal: 4 to 20 mAdc and 1 to 5 Vdc.
Supply voltage: Refer to Model Chart.
Mechanical Action: Direct acting output rises as input increases.
Adjustments Refer to Figure 1.
Environment
Ambient temperature limits
Shipping and handling: -40 to 160°F (-40 to 71°C).
Operating: 40 to 140°F (4 to 60°C).
Temperature stability Typically ±0.03% of output span per °F between 40 and 140°F.
Humidity 5 to 95%, non-condensing.
Location NEMA Type 1.
Dimensions 3-7/8 H x 5 W in. (98 x 127 mm).
Agency Listing UL File E71385.
CUL.
General Instructions Refer to F-20091.
-
8311