Accessory List

MS51-7103 Series, MSx1-7203 Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 193
Typical Applications
Vdc
Feedback Signal
Red
Blk
Com
Hot (+DC)
Line
Volts
(-)
(+)
(-)
(+)
Vdc or mAdc
Control Signal
Yel/Blk
AI
1
MS51-7103-xxx
mAdc or Vdc Proportional Control
Violet AO
24 Vac Transformer
or 20-30 Vdc
2
3
4 5
1 Provide overload protection and disconnect as
required.
2 Actuators may be wired in parallel.
All actuator black wires are connected to
the transformer common and all red wires are
conn
ected to the hot lead. Power consumption must
be observed.
3 If the controller uses a full-wave power supply and
does not provide isolated outputs, a separate
transformer is required.
4 On MS51-7103-x60 (4-20 mAdc) models a 500
ohm resister is incorporated in the product. Do
not use an external resistor.
5 Cable on some models contains more wires
than are used in app
lications. Only those
wires actually used are shown.
Figure 1 Vdc Proportional Control.
To Additional
2-10 Vdc
Actuators
Hot (+DC)
Red
Blk
Com
Line
Volts
(-)
(+)
Control Signal
4 to 20 mAdc
Yel/Blk
Violet
(-)
(+)
Feedback Signal
2 to 10 Vdc
4
AI
AO
MS51-7103-x00
5
1
500
24 Vac Transformer
or 20- 30 Vdc
2
2
3
4
1 Provide overload protection and disconnect as
required.
2 Actuators may be wired in parallel.
All actuator black wires are connected to
the transformer common and all red wires are
conn
ected to the hot lead. Power consumption must
be observed.
3 If the controller uses a full-wave power supply and
does not provide isolated outputs, a separate
transformer is required.
4 Cable on some models contains more wires
than are used in applications. Only those
wires actually used are shown.
5 AM-708 load resistor to convert signal to 2 to 10 Vdc.
Figure 2 4 to 20 mAdc with 2 to 10 Vdc Actuators.
Red
Blk
Com
Hot (+DC)
Line
Volts
(-)
(+)
Yel/Blk
AI
Red
Blk
Com
Hot (+DC)
Yel/Blk
AI
Violet
AO
Violet
AO
MS51-7103-xxx
MS51-7103-xxx
1
Control Signal
24 Vac Transformer
or 20-30 Vdc
2 3
2 3
(-)
(+)
Feedback Signal
1 Provide overload protection and disconnect as
required.
2 Actuators may be wired in parallel.
All actuator black wires are connected to
the transformer common and all red wires are
conn
ected to the hot lead. Power consumption must
be observed.
3 Cable on some models contains more wires
than are used in applications. Only those
wires actually used are shown.
Figure 3 Proportional Control 24 Vdc Models Wired in Parallel.