Accessory List

MS40-7043, MS41-7073, MS41-7153
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 169
Typical Applications
MS40-7043
MS40-7043-501
24 Vac
Transformer
Red
Black
Common
Hot
1
Line
Volts
(-)
(+)
Control Signal
2 to 10 Vdc
Yellow/Black
AI
1 Provide overload protection
and disconnect as required.
2 Actuators may be connected
in parallel. Power
consumption and input
impedance must be observed.
L R
2
Green/Yellow
Common
Grey
Figure 1 2 to 10 Vdc Control of MS40-7043 and MS40-7043-501 Actuator.
Hot
MS40-7043
MS40-7043-501
24 Vac
Transformer
Red
Black
Common
1
Line
Volts
(-)
(+)
Control Signal
4 to 20 mA
Yellow/Black
AI
Blue
AO
500 Ω
(-)
(+)
Feedback Signal
2 to 10 Vdc
To other
actuators
Ω
1 Provide overload protection and
disconnect as required.
2 For unison operation in 4 to 20 mA
applications, actuators may be
wired in series and mounted on
separate shafts. Also, up to four
actuators, mounted on separate
shafts may be wired in parallel.
With four actuators wired to one
500 ohm resistor, a +2% shift of the
control signal may be required.
Power consumption and input
impedance limits must be
observed. Actuator input
impedance is 80 kohm.
3 For end position indication, interlock
control, fan startup, etc., MS40-
7043-501 model incorporates one
built-in auxiliary switch.
4 To reverse actuator rotation, use
the reversing switch.
5 A field supplied 500 ohm resistor
(AM-708) is required between the
gray and yellow/black leads to
convert the 4 to 20 mAdc control
signal to 2 to 10 Vdc.
6 Only connect common to negative
(-) leg of control circuits.
5
4
4
L R
2
Common
Grey
Green/Yellow
6
3