Accessory List
MPR-5600 Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 161
Typical Applications
Figure 1 Wiring Diagram 4 to 20 mAdc Controllers.
Restrictions on Maximum Ambient Temperature for Valve Actuators.
Maximum Temperature of Media in the
Valve Body (Check Rating of the Valve)
°F (°C)
Maximum Ambient Temperature of MPR-561x and MPR-573x Series.
AV-600 (only)
°F (°C)
AV-600 and AV-601
°F (°C)
366 (186)
Do Not Use
88 (31)
a
a
Minimum allowable ambient temperautre of the actuators is -20°F (-29°C).
340 (171) 93 (34)
281 (138) 103 (39)
b
b
Maximum allowable ambient temperature of the actuator must never exceed 140°F (60°C).
181 (83) 120 (48)
b
80 (26) 140 (60)
b
140 (60)
b
1
2
From AC
Power Source
Controller
4 to 20 mAdc output signal
MPR-561x
MPR-563x
Yellow/White
Red
+
-
Black
1 24 Vac Black/Blue
120 Vac White
240 Vac White/Black
2 Actuator startpoint adjuster is located
behind the plug button on the base.