Accessory List

MPR-5600 Series
160
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Specifications
Accessories
Actuator inputs
Control circuit MPR-561x and -563x series: Two-wire. 4 to 20 mA.
Input impedance 82.5 Ω for 40 to 20 mA input.
Power input Refer to Valve (Basic) Actuators Model Chart and Damper Actuators Model Chart.
Connections Color coded 4 ft. (1.2 m) leads.
Actuator outputs
Electrical
Position signals: Internal feedback circuitry provides positive positioning of the damper in relation to
the controller signal.
Startpoint adjustment: Adjustable potentiometer provides manual adjustment of the actuator
startpoint.
Mechanical
Stroke damper: Approximately 2 in. (51 mm) from fully retracted to fully extended (includes AM-601
linkage).
Valve: Approximately 9/16 in. (14 mm) from fully retracted to fully extended.
Nominal damper area: Actuator sizing should be done in accordance with damper manufacturer’s
specifications.
Proportional output torque rating of 15 lb-in. (1.7 N-m), available throughout the entire stroke, based
on the lowest force available under normal operation, the spring return stroke, or at a minimum
(-10%) supply voltage.
Environment
Ambient temperature limits
Shipping and storage: -40 to 140°F (-40 to 60°C).
Damper: -20 to 140°F (-29 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Location NEMA Type 1.
Dimensions
MPR-5x1x series 6 -3/4 H x 3 -1/4 D in. (171 x 83 mm).
MPR-5x3x series 10 H x 4 -1/4 W x 9 -1/2 D in. (254 x 108 x 241 mm).
Timing in Seconds at 72°F (22°C)
No load stroke
Extend: 60.
Retract: 30.
Retract on power loss 15.
Agency Listings
UL 873 Underwriters Laboratories File E9429 Category Temperature-Indicating and Regulating Equipment.
CUL Certified for use in Canada by Underwriters Laboratories. Canadian Standard C22.2 No. 24-93.
European Community EMN Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
General Instructions Refer to F-23576.
Model No. Description
Damper Linkages
AM-111 Crank arm for 5/16 in. (7.9 mm) diameter damper shaft.
AM-112 Crank arm for 3/8 in. (9.5 mm) diameter damper shaft.
AM-113 Crank arm for 1/2 in. (12.7 mm) diameter damper shaft.
AM-115 Crank arm for 7/16 in. (11.1 mm) diameter damper shaft.
AM-122 Linkage connector straight type.
AM-123 Damper clip.
AM-125 5/16 in. diameter x 20 in. (7.9 x 508 mm) damper rod.
AM-125-048 5/16 in. diameter x 48 in. (7.9 x 1,219 mm) damper rod.
AM-132 Ball joint connector.
AM-161-3 Damper linkage kit.
AM-601 Device includes mounting bracket, damper linkage with spring, and AM-122 straight connector. Required to
modify (MPR-5x1x series) valve actuators into 2 in. (51 mm) stroke damper actuators.
AM-602 Spacer.
Valve Linkages and Valves
AV-600 Valve linkage for 1/2 to 2 in. VB-7xxx and discontinued VB-9xxx valves.
AV-601 Valve linkage extension for hot water and steam applications. Use with AV-7600-1.
AV-7600-1 Valve linkage for VB-7xxx.
Tools (factory available)
TOOL-19 Spring compression tool for AV-600.
TOOL-209 135 Ω and 0 to 7 mA manual positioner.