Accessory List

MP-9xxx Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 157
Accessories
Typical Applications
Figure 2 Typical Reversible Floating or Two-Position
.
Figure 3 Typical Proportional Electric.
Model No. Description
Damper Linkage Accessories
AE-504 100 to 1000 Ω input actuator drive.
AM-321 Two step switch kit.
AM-332 100 Ω single potentiometer.
AM-341 Four step switch kit.
AM-342 Two step switch and potentiometer kit.
AM-345 Actuator mount, time delay relay for MP-9810, MP-9830 and MP-9910, field modified for panel mounting.
AM-369 NEMA 4 gasket kit.
a
a
Back cover plate prevents the use of other accessory kits.
AM-392 Crank arm for actuator, 1/2 in. slot provides for adjustable radius from 1 in. (25 mm) to 5 in. (127 mm), zinc
plated.
AM-394 Connecting link, two (2) 1/2 in. dia. threaded rods with turnbuckle and two (2) 1/2 in. dia. ball joint
connectors, adjustable from 15-3/4 to 24-3/4 in.
CYZR-818-3 Arc suppressor.
1 SPDT Neutral Off Switch may be used on manual
positioning applications.
2 Switch control circiut is 0.9 amp at approx. 24 Vac
on either low or line voltage actuators.
3 Terminals 1,5,& 6 are used for built-in auxiliary
switch.
4 Rotates CW or valve stem down.
5 Rotates CCW or valve stem up.
6 These terminal are marked L1 & L2 on line voltage
actuators.
7 External green Jumper from X to case ground on
MP-xxxx-xxx-x-2 models only.
6
7
5
4
3
1 2
6
3
MP-9713
MP-9750
H
G
2
X
AC Supply
SPDT Floating Control
or Two-Position
Switch
CYZR-818-3
Arc Suppressor
purchased separately
White
Blue
Red
7
5
6
3
4
2
1
1
7
H
5
G
8
PP-220
Series
Typical
Controller
B
C
R
1 Terminals 1, 5, & 6 are used for built-in auxillary switch.
R-Closes on pressure drop and rotates actuator CCW.
B-Closes on pressure rise & rotates actuator CW.
C-Common.
1 -Feedback.
2 Rotates CW or valve stem down.
3 Rotates CWW or valve stem up.
4 External green jumper X to case ground on
MP-xxxx-xxx-x-2 Models only.
5 These terminals marked L1 & L2 on line voltage actuators.
Line voltage actuators require built-in transformer.
6 Built-in transformer leads on line voltage actuator.
7 Make resistor and jump connection on 24V actuators only.
MP-9713
MP-9750
4
3
2
1
2
X
100 Ω
AC Supply