Accessory List
MP-54xx Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 149
CAUTION: Avoid condensation which can facilitate corrosion. With 40°F (4°C) water, the maximum allowable ambient dew
point temperature is 68°F (20°C). Piping insulation must not stop drainage at actuator mounting nut. Do not use Hydraulic
Actuators with fluid temperatures below 40°F (4°C).
Specifications
Maximum Allowable Ambient Air Temperature for Valve Actuators.
Temperature of Media in the Valve Body
(Check the Rating of the Valve) °F (°C)
Maximum Allowable Ambient Air Temperature of MP-541x Series
AV-600
a
or AV-7600-1
b
Only for Chilled
Water Applications °F (°C)
a
For detailed valve linkage installation instructions, refer to AV-600 Hydraulic Actuator Valve LInkage Kit General Instructions, F-26279.
b
For detailed valve linkage installation instructions, refer to AV-7600 Hydraulic Actuator Valve LInkage Kit General Instructions, F-26235.
AV-600
a
or AV-7600-1
b
with AV-601 Extension
°F (°C)
366 (180)
Do Not Use
88 (31)
340 (171) 93 (34)
281 (138) 103 (39)
181 (83) 120 (48)
80 (26) 140 (60)
c
c
Maximum allowable ambient temperature of the actuator.
140 (60)
c
Inputs Compatible with 2 to 15 Vdc from TAC System 8000 controllers.
Operating span Approximately 3 Vdc fixed.
Start point Adjustable 2 to 12 Vdc. Factory set at 6 Vdc. Impedance 10,000 Ω or greater.
Power Refer to Damper Actuators Table and Valve Actuators Table.
Connections Color-coded 4 ft (1.2 m) leads.
Outputs
Electrical Internal Power Supply: 20 Vdc, 25 mA.
Mechanical
Stroke, Damper: Approximately 2 in. (51 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully
extended) input range (includes AM-601 linkage).
Stroke, Valve: Approximately 9/16 in. (14 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully
extended) input range.
Nominal Damper Area: Actuator sizing should be done in accordance with damper manufacturer’s
specifications.
Environmental
Ambient temperature limits
Operating: -20 to 140°F (-29 to 60°C).
Damper: -20 to 140°F (-29 to 60°C).
Valve: Refer to Maximum Allowable Ambient Air Temperature for Valve Actuators.
Humidity 5 to 95% RH, non-condensing.
Location NEMA Type 1.
Dimensions 6-3/4 H x 3-23/32 W x 3-1/4 D in. (171 x 18 x 83 mm).
Agency Listings
UL UL873 File E9429 Temperature Indicating and Regulating Equipment.
CUL Canadian Standard (File #LR3728).
European Community EMC Directive 89/336/EEC, Low Voltage Directive 72/23/EEC.
General Instructions Refer to F-24788.