Accessory List

MP-54xx Series
148
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Electronic Positive Positioning Hydraulic Actuator
Model Chart
These actuators provide electronic proportional
control of dampers, valves, or program switches
requiring the return to normal position upon power
interruption.
Features:
Proportional control by variable Vdc input signal.
Compatibility with 2 to 15 Vdc TAC System 8000 input
signals.
•Spring return.
Fixed 3 Vdc operating span.
Adjustable 2 to 12 Vdc start point for paralleling or
sequencing of actuators.
10,000 Ω or greater input impedance.
24 Vac, 120 Vac, and 240 Vac models.
Damper models with linkage or base models that require
separate damper or valve linkage.
Die cast lower housing with 1/2 in. conduit opening and
painted steel upper housing.
Hydraulic actuator with oil immersed motor, transducer,
and pump.
Damper Actuators.
Model No.
Actuator Power Input
Positive
Positioner
a
a
Internal feedback circuitry provides positive positioning of the damper in relation to the controller signal.
Timing in Seconds at 72°F (22°C)
Torque Rating
lb-in. (N-m)
AC Voltage
+10/-15%
50/60 Hz No Load Stroke
Retract on
Power Loss
Watts VA To Extend To Retract
MP-5430 120
18 10 Yes 60 30 15
15
(1.69)
MP-5433 240
Valve Actuators. Also for Damper Actuators with Field Assembled Damper Linkages.
Model No.
Actuator Power Input
Positive
Positioner
a
a
Internal feedback circuitry provides positive positioning of valve stem in relation to control signal.
Timing in Seconds at 72°F (22°C)
Required Linkage
No Load Stroke
Retract
on Power
Loss
Damper Valve
AC Voltage
+10/-15%
50/60 Hz
To Extend To Retract
Watts Amps
MP-5410 120
18 10 Yes 60 30 15 AM-601
b
b
With the installation of the AM-601 damper linkage, these valve actuators become functionally the same as the damper actuators listed under Damper
Actuators.
AV-600 or
AV-7600-1
AV-601
c
c
May be required for steam and hot water. Refer to Maximum Allowable Ambient Temperature for the Valve Actuator.
MP-5411 240
MP-5413 24
MP
-
54
xx
Series