Accessory List

680 Series
4
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
TAC Erie™ Seasonal Changeover Switch
Model Chart
See TC-2931/2942 for other models.
Specifications
The 680 series low or line voltage changeover
switches are designed to switch a thermostat from
heating to cooling based on a change in supply
water temperature. The 680 series switches can be
mounted on 5/8 in. or 7/8 in. O.D. copper tube or
iron pipe.
Both models are easily mounted to the supply
piping with a simple spring clip included with the
thermostat. Each thermostat also includes the
necessary wire nuts and strain relief bushing.
Features:
Add-on switch for seasonal change over.
Includes all necessary parts for installation.
Snap acting SPDT.
Model No. Voltage
Inductive
Resistive Amps Description
FLA LRA
680-243-5
120 5.8 34.8 10
Standard changeover switch
240 2.9 17.4
5
680-243-6
120 10.0 60.0
25
Includes a conduit
connection
240
5.0 30.0
25
Inputs
Connections Color coded leads, 36 in (914 mm).
Outputs
Mechanical
Changeover temperature range: Below 65 ±5°F white and blue (cool) make, above 83 ±5°F white
and black (heat) make.
Environment
Ambient temperature limits
Shipping and storage: -20 to 176°F (-29 to 80°C).
Operating: 220°F (104°C) fluid at ambient temperature of 125°F (52°C)
Locations NEMA Type 1.
Agency Listings
UL Listed UL-873, Underwriters Laboratories Listed (File #E29653).
CSA Canadian Standards File #LR10281.
General Instructions Refer to F-26932.
680
S
er
i
e
s