Accessory List

MP-52xx Series
146
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
CAUTION: Avoid condensation which can facilitate corrosion. With 40°F (4°C) water, the maximum allowable ambient dew
point temperature is 68°F (20°C). Piping insulation must not stop drainage at actuator mounting nut. Do not use hydraulic
actuators with fluid temperatures below 40°F (4°C).
Specifications
Maximum Allowable Ambient Air Temperature for Valve Actuators.
Temperature of Media in the Valve Body
(Check the Rating of the Valve) °F (°C)
Maximum Allowable Ambient Air Temperature of MP-52xx Series
AV-600 or AV-7600-1 Only for Chilled
Water Applications °F (°C)
AV-600 or AV-7600-1 with AV-601 Extension
°F (°C)
366 (180) 90 (32) 90 (32)
340 (171) 100 (38) 100 (38)
281 (138) 115 (46)
140 (60)181 (83)
140 (60)
80 (26)
Actuator inputs
Compatible with
2 to 15 Vdc from TAC System 8000 controllers.
Operating span: Approximately 3 Vdc fixed on damper. See F26235-2 for valves.
Start point: Approximately 6 Vdc fixed. See F-26235-2 for valves.
Impedance: 10,000 Ω or greater.
Power input Refer to Damper Actuator Model Chart, and Valve Actuator Model Chart.
Connections Color coded 4 ft. (1.2 m) leads.
Actuator outputs
Electrical
Internal power supply: 20 Vdc, 25 mA.
Auxiliary switch (MP-52XX-500): 10 amps, 120/240 Vdc adjustable SPDT, factory set to close N.C.
contact at retracted end of stroke.
Mechanical
Stroke, Damper: Approximately 2 in. (51 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully
extended) input range. Includes AM-601 linkage.
Stroke, Valve: Approximately 9/16 in. (14 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully
extended) input range.
Nominal damper area: Actuator sizing should be done in accordance with damper manufacturer’s
specifications.
Environment
Ambient temperature limits
Shipping and handling: -40 to 140°F (-40 to 60°C).
Operating: -20 to 140°F (-29 to 60°C) for damper actuators.
For valve actuators, refer to Maximum Allowable Ambient Air Temperature for Valve Actuators.
Humidity 5 to 95% RH, non-condensing.
Location NEMA Type 1.
Dimensions 6-3/4 H x 3-1/4 W in. (171 x 83 mm).
Agency Listings
UL File E9429 Temperature Indicating and Regulating Equipment.
CUL Canadian Standard C22.2 #24-93.
European Community EMC Directive 89/336/EEC, Low Voltage Directive 72/23/EEC.
General Instructions Refer to F-24789.