Accessory List
MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 143
Figure 4 Typical for Proportional Slidewire.
Figure 5 Typical Proportional Electronic ⎯ Voltage.
Wiring for MP-461-600, MP-471-600, MP-481-600.
1
1
2
3
3
2
4
7
H
G
8
AE-504
Parallel
Relay
Slidewire Input
Blue/Black
Yellow/Black
Red/Black
MP-300
MP-400
MP-2000-500
MP-4000
Series
Actuator
3
2
Green
X
AC Supply
Brown/Yellow
4
1 Resistor & jumper
present on 24V
actuators only.
2 These terminals
marked L1 and L2 on
line voltage actuators.
3 Direction actuator will
drive.
4 Case ground screw.
Factory
Installed
to the
Actuator
CCW
CW
Black
Brown
680Ω
50Ω
680Ω
TP-8101
CP-8102
4
3
2
2
1
6
5
7
L2
L1
8
CP-8301-120
CP-8301-024
CP-8301-240
Solid State
Actuator
Drive
Blue/Black
Yellow/Black
Red/Black
MP-300
MP-400
MP-400-600
MP-2000-500
MP-4000
Series
Actuator
3
2
X
120 Vac
AC Supply
Brown
4
Blue
Yellow
Red
COM (Blue)
OP (Yellow)
+20 (Red)
1 Typical controllers.
2 Actuator rotates clockwise on increase
in input signal. To rotate actuator
counterclockwise on an increase in
input signal reverse Blue/Black and
Red/Black leads and reverse
Brown/Black and Brown/ White leads.
3 Terminals 1, 5 & 6 are used for built-
in auxilliary switch. 1- 5NC, 1 -ENO
4 Only 24 Vac actuators have this
ground.
5
6 20 Vdc. 50 mA power supply in
CP-8301-xxx.
Factory
Installed
to the
Actuator
Brown/White
Brown/Black
Black
Part Number Vac
Color
CP-8301-120
White
Black/Blue
CP-8301-024
CP-8301-240
120
24
240
White/Black