Accessory List

MP-3xx Series, MP-4xx Series, MP-2xxx Series, and MP-4xxx Series
138
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
MP-4xx Series
Model No. Application
Solid
State
Drive
CP-9301
CP-9302
Power
Requirements
Output Shaft
Aux.
Switch
Built-in
Transformer
a
Volts Hz Amps
Torque
lb.-in.
(N-m)
Timing
Seconds
(No Load)
Degrees of
Rotation
Spring
Return
MP-421
Proportional Available
120
60
0.65
60 (6.8)
25
180 (Adj.
b
)
No
SPDT
MP-422
25 to 250
(Adj.)
MP-423 13
90 (Adj.
b
)
MP-424
13 to 130
(Adj.)
MP-451
220
(24.9)
80
180 (Adj.
b
)
MP-452
80 to 800
(Adj.)
MP-453 40
90 (Adj.
b
)
MP-454
40 to 400
(Adj.)
MP-461-600
refer to
footnote
c
CP-8301-
120
Included
0.5
50 (5.6) 90
180 (Adj.
b
)CW
MR-461-691 CP-9301
MP-465 Proportional Available
Yes
MP-470
Five
position
180 (non-Adj.) CCW
None
MP-471-600
refer to
footnote
c
CP-8301-
120
Included
SPDT
MP-471-691
CP-9301
Included
MP-475 Proportional Available
Yes
MP-480
Five
position
220
(24.9)
130 180 (Adj.
b
)
No
None
MP-481 Proportional Available SPDT
MP-481-600
refer to
footnote
c
CP-8301-
120
Included
SPDT
MP-481-691
c
CP-9301
Included
MP-483
Proportional Available
65 90 (Adj.
b
)
Yes
MP-485 130
180 (Adj.
b
)
MP-486
130 to 1300
(Adj.)
MP-495 0.95
450
(50.9)
130
MP5-483 50 0.5
220
(24.9)
78 90 (Adj.
b
) No SPDT
a
Units with a “-2” suffix, e.g. MP-xxxx-xxx-2-x, include a built-in transformer (used for Microtherm or with AE-504) with secondary loads wired externally to
terminals seven and eight of the actuator. Red (24 Vac) to terminal eight and Blue (12 Vac) to terminal seven. When these actuators are used with con-
trollers other than Microtherm or AE-504, disconnect the Red and Blue leads and tape off. Note: Models prior to “-2” suffix had transformer wired directly
to potentiometer. To disconnect the transformer, remove the back plate of the actuator, disconnect, and tape the transformer leads.
b
Rotation adjustable 45 to 320°. Caution: On actuators with proportional input signals changing the rotation will affect the control, since the internal feed-
back potentiometer’s travel is fixed.
c
6 to 9V proportional.