Accessory List

MMC Series
136
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Control Module
Model Chart
Specifications
Accessories
For MM, MMR 400 and 500 series actuators.
These plug in control modules are used with the
MM-400, MM-500, MMR-400, and MMR-500 Series
actuators.
Features:
Plugs into the MM, and MMR actuators.
Accepts various control signals.
Johnson and Honeywell interface models.
Economizer control models.
Model No.
Control Signals Adjustments
Competitor
Interface
Analog
Al
Digital
Dl
Start
Point
Span
Throttling
Range
Mix Air
Set
Point
Minimum
Position
Electrical/Mot
or Stroke
Complete
Application
Information
MMC-90
a
a
Refer to Complete Application Information column for details.
Honeywell/
Johnson
135 ohm
0 to 7
mAdc
SPST or
SPDT
——
——Yes
b
b
Remote minimum positioner optional.
Yes F-23350
MMC-401
c
c
Economizer Control.
10K
Thermistor
Yes 2 to 20 F°
40 to
65°F
0 to 50% No F-23493
MMC-420 4 to 20 mA Yes
———
Yes F-23786
MMC-468
a
Honeywell/
Johnson
SPST or
SPDT
No F-23349
MMC-421 4 to 20 mA
Adjust-
able
2 to 20
mA
Yes
F-24160
MMC-8000
a
Johnson
4 to 20 mA/
6 to 9 Vdc
2 to 20
mA/
1 to 20
Vdc
F-23351
Power requirements 24 Vac +10/-15%, 50/60 Hz, 3.9 VA.
Power supply available
MMC-420 and MMC-8000 only: 20 Vdc ±1 Vdc, 35 mA (regulated and filtered power supply that
cannot be paralleled with another supply).
Environment
Ambient temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: -40 to 140°F (-40 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations Mounted in MM or MMR series of actuators.
Dimensions 1-1/8 H x 3-1/2 W x 2-1/2 D in. (29 x 89 x 64 mm).
Model No. Description
AM-236-300 Remote minimum positioner.
TS-5721-102 Thermistor (MMC-401 only).
TC-4115 Outside air thermostat (MMC-401).
THCR-4 Enthalpy controller (MMC-401).
MMC
S
e
r